Chapter 6
6-13
Troubleshooting
UPS Running on AC Power with Audible Alarm
• The UPS has been placed in Service Bypass (see “Service Bypass” in
Chapter 4).
Abnormal causes of this case are:
• The UPS microprocessor detected a UPS internal failure and placed the
unit in Automatic Bypass mode.
• The Battery Box cable is not connected to the UPS Electronics Unit.
• The Battery Precharge Shorting Plate is not properly installed onto the
corresponding connector blades of the Electronics Unit.
• Deeply discharged (or dead) UPS batteries.
Action:
1. Verify whether the Service Bypass switch is in the
BYPASS
position; if so,
use the procedure in “Taking the UPS Out of Service Bypass Mode” in
Chapter 4 to recover the UPS from Service Bypass.
2. If the Service Bypass switch is in the
NORMAL
position, the UPS must be
in Automatic Bypass. To determine if it got to this state because of an
internal UPS fault or by the normal depression of the red Bypass
Switch Activation Button, turn the Output On/Output Off switch to
Output Off
for one second, and then turn it back to
Output On
.
If the UPS returns to normal (UPS Running on AC Power), then it is
either OK (and must have gotten into Automatic Bypass by normal
depression of the red Bypass Switch Activation Button) or else it has an
intermittent fault that occasionally puts it in Automatic Bypass and
then clears itself.
If the UPS remains in the condition described in this case (with the
Service Bypass switch in the
NORMAL
position and after toggling the
Output On/Output Off switch), it must be defective.
Case 5 (Normal) — Overload Warning On-Line
Indicators:
AC Output
lit
Battery Power
not lit
Attention
flashes once per second
Caution LED not lit
Enable lit
Audible Alarm: 1 beep every 10 seconds
Meaning:
Indicates an overload condition while the UPS is running On-line. (The
loads attached to the UPS output require more power than the UPS can
support while running On-line).
Cause:
Excessive UPS load.
Содержание PowerTrust A3589A
Страница 7: ...Contents Contents 5 ...
Страница 8: ...Contents 6 Contents ...
Страница 10: ...Contents 8 Figures ...
Страница 12: ...Contents 10 Tables ...
Страница 14: ...2 ...
Страница 20: ...Preface 8 ...
Страница 22: ...Preface 10 ...
Страница 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Страница 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Страница 62: ...1 40 Chapter1 Overview Support Information ...
Страница 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Страница 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Страница 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Страница 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Страница 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Страница 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...