Appendix A
A-17
HP-UX UPS Monitor Error Messages
reboot(2) Messages
MESSAGE
ups_mond: UPS <tty special file name> ambient temperature
too high; UPS turned itself off - reduce heat in area
SEVERITY
Critical. PowerTrust hardware has failed, and PowerTrust output power has
been lost. Some system component(s) now without power.
MEANING
The PowerTrust device configured as <tty special file name> informed the
UPS Monitor that it detected an excessive ambient temperature that makes
further operation of the PowerTrust unit inadvisable, and has consequently
shut off its output. If the specified PowerTrust unit is a critical PowerTrust
unit, then the system will reboot.
CAUSE
The computer room became so hot that the operating temperature limit of the
PowerTrust unit was exceeded.
ACTION
Reduce the temperature in the computer room.
Содержание PowerTrust A3589A
Страница 7: ...Contents Contents 5 ...
Страница 8: ...Contents 6 Contents ...
Страница 10: ...Contents 8 Figures ...
Страница 12: ...Contents 10 Tables ...
Страница 14: ...2 ...
Страница 20: ...Preface 8 ...
Страница 22: ...Preface 10 ...
Страница 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Страница 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Страница 62: ...1 40 Chapter1 Overview Support Information ...
Страница 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Страница 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Страница 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Страница 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Страница 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Страница 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...