D-10
Appendix D
Field Replaceable Units
Removal and Replacement Procedures
4. Use a screwdriver to loosen the screw at the center of each captive thumbscrew on the
Battery Precharge Shorting Plate, then unscrew the thumbscrews and remove the
plate. See Figure 3-8.
5. Disconnect the Battery Box cable from the Electronics Unit.
6. Remove the filler panels from in front of the battery box.
7. Using the procedure outlined in “Removing Battery Packs from Battery Box” in
Chapter 2, remove the battery packs from the Battery Box.
8. Remove the two screws at each corner of the Battery Box (eight total) from the cabinet
frame. See Figure 3-8.
9. With the help of another person, slide the old Battery Box out of the rack.
10.Slide the new Battery Box into the rack.
11.Reattach the two screws at each corner of the Battery Box (eight total) to the cabinet
frame.
12.Install all ten battery packs:
• Replace batteries on one side one a a time moving from left to right.
• Replace the batteries on the other side one at a time moving from left to right.
• Make sure to tighten the thumbscrew at the bottom of each battery pack.
13.Reattach the Battery Box cable to the Electronics Unit.
After you attach the cable, the capacitors will precharge.
14.Check the Battery Precharge Failure LED (see
15
in Figure 1-3).
If the LED is off, continue.
If the LED is on, do not reinstall the Battery Precharge Shorting Plate. Refer to
“Case 14 (Abnormal) — Battery Precharge Failure” in Chapter 6.
15.Orient the plate so that the notch on the plate is positioned over the Battery Box cable
connector, then reattach the plate making sure that the prongs on the plate are pressed
firmly into the clips in the Electronics Unit. See Figure 3-9.
You may need to rock the plate back and forth as you push it in.
CAUTION
Operating the UPS without the Battery Precharge Shorting Plate is not
supported and may result in loss of UPS AC output.
16.Fasten the thumbscrew at the bottom of the battery pack.
17.Put the old battery pack in the shipping container from which you took the new battery
pack and follow the return and disposal procedures that were shipped with the
replacement battery pack.
18.Repeat steps 7 through 12 for the remaining battery packs on one side of the Battery
Box. When you finish replacing the battery packs on one side, replace the battery packs
on the other side, one at a time. Begin with the left-most battery pack.
Содержание PowerTrust A3589A
Страница 7: ...Contents Contents 5 ...
Страница 8: ...Contents 6 Contents ...
Страница 10: ...Contents 8 Figures ...
Страница 12: ...Contents 10 Tables ...
Страница 14: ...2 ...
Страница 20: ...Preface 8 ...
Страница 22: ...Preface 10 ...
Страница 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Страница 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Страница 62: ...1 40 Chapter1 Overview Support Information ...
Страница 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Страница 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Страница 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Страница 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Страница 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Страница 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...