Appendix A
A-37
HP-UX UPS Monitor Error Messages
Log-Only Messages
MESSAGE
ups_mond: UPS <tty special file name> Low Battery Voltage -
requires repair
SEVERITY
Critical. PowerTrust hardware has failed. PowerTrust power output is still on,
but the PowerTrust unit will not be able to protect the system against an AC
power failure, if one occurs.
MEANING
The PowerTrust device configured as <tty special file name> informed the
UPS Monitor that the voltage output of its battery is too low. The PowerTrust
unit can no longer be relied upon to supply battery reserve power in the event
of an AC power failure.
CAUSE
A hardware problem in the battery or battery charger circuitry, or elsewhere
in the PowerTrust unit, has caused the battery to fail to perform normally.
ACTION
Call HP Service.
Содержание PowerTrust A3589A
Страница 7: ...Contents Contents 5 ...
Страница 8: ...Contents 6 Contents ...
Страница 10: ...Contents 8 Figures ...
Страница 12: ...Contents 10 Tables ...
Страница 14: ...2 ...
Страница 20: ...Preface 8 ...
Страница 22: ...Preface 10 ...
Страница 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Страница 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Страница 62: ...1 40 Chapter1 Overview Support Information ...
Страница 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Страница 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Страница 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Страница 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Страница 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Страница 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...