6 Using the heating system – Structure of the menus
139
10-12
Heat circuit 1
Maximum
Supply temperature
( 45) 45°
•
Maximum supply temperature
Set the maximum supply temperature.
(20 - 90 °C)
10-13
Heat circuit 1
Minimum
Supply temperature
( 25) 25°
•
Minimum supply temperature
Set the minimum supply temperature.
(20 - 50 °C)
10-14
Heat circuit 1
Enabling temperature
Heat circuit pump
( 40) 40°
•
Enable temperature for the heating circuit pump
If the boiler temperature (without accumulator) or the
“Acc. top” temperature (with accumulator) is above the
preset value, the heating circuit pump is enabled. (20 -
100 °C)
10-17
Heat circuit 1
Mixing valve runtime
( 150) 150s
•
Mixing valve runtime
Set the mixing valve runtime.
(10 - 300 s)
10-18 Screed drying
no
yes
•
Screed drying program
Activate the screed drying program.
10-19 Heat circuit 1
Set supply temp.
increase
Screed drying
( 5) 5°
•
Increase in room temperature
Set the increase in room temperature for screed drying.
(1 - 10 °C)
10-20 Rise HC1
Every day
After two days
After three days
After four days
After five days
•
Day cycle temperature increase
Set the day cycle for the preset temperature increase.
10-21 Heat circuit 1
Set min. supply temp.
Screed drying
( 20) 20°
•
Minimum supply temperature for screed drying
Set the minimum supply temperature for screed drying.
(10 - 30 °C)
10-22 Heat circuit 1
Set max. supply temp.
Screed drying
( 45) 45°
•
Maximum supply temperature for screed drying
Set the maximum supply temperature for screed drying.
(25 - 60 °C)
No.
Display
Description
Table 6/12 - System level / 10 - Heating circuit 1