5 Commissioning the system – Procedure
91
✓
The actuators have been checked.
C
HECKING
THE
SENSORS
IN
MANUAL
OPERATION
1.
Switch to manual operating mode.
✎
See the chapter entitled “6 Using the heating system”, section
“6.6 Changing operating mode”.
2.
After selecting the respective sensor, press the
Up
or
Down
button.
h-07
Automatic grate
Off
Limit switch
Start (+)
Stop (-)
Automatic grate
Plus
button: Grate tips down
Minus
button: Grate tips up
h-08
Cleaning system
Off
Limit switch
Start (+)
Stop (-)
Cleaning system
Plus
button: Cleaning system switches on
Minus
button: Cleaning system switches off
h-11
Primary air
flap
0%
plus 1%
(+)
minus 1%
(-)
Servo motor for primary air
Plus
button: Servo motor for primary air opens percentu-
ally
Minus
button: Servo motor for primary air closes percen-
tually
h-12
Secondary air
flap
0%
plus 1%
(+)
minus 1%
(-)
Servo motor for secondary air
Plus
button: Servo motor for secondary air opens percen-
tually
Minus
button: Servo motor for secondary air closes per-
centually
h-13
Ignition fan
Fan
Off
Heating
Off
Start (+)
Stop (-)
Ignition fan
1 x
Plus
button: Fan switches on
2 x
Plus
button: heater also switches on
Minus
button: Ignition fan switches off
h-14
Return mix. valve
Off
Open (+)
Close (-)
Return mix. valve
Plus
button: Return mixing valve is opened
Minus
button: Return mixing valve is closed
h-15
Return pump
Off
Start (+)
Stop (-)
Return pump
Plus
button: Return pump switches on
Minus
button: Return pump switches off
No.
Display
Description
Table 5/6 - Actuators in manual operation