6 Using the heating system – Structure of the menus
119
2-06
Boiler
Set temperature for
external demand
( 70)
70°
•
Preset boiler temperature for an external demand
If the boiler is controlled externally, this is where the desi-
red target temperature for the boiler is set. (20 - 100°C)
2-10
Enabling boiler
Mo Tu We Th Fr Sa Su
On 00:00 On 00:00
Off 24:00 Off 00:00
•
Enabling boiler
Time block 1: Various enable times can be defined for the
individual days of the week.
✎
See page 103.
2-11
Enabling boiler
Mo Tu We Th Fr Sa Su
On 00:00 On 00:00
Off 00:00 Off 00:00
•
Enabling boiler
Time block 2: Various enable times can be defined for the
individual days of the week.
✎
See page 103.
2-12
Boiler
Set temperature for
chimney sweep mode
( 80)
80°
•
Preset temperature for chimney sweep test
This is the boiler preset temperature at which the chim-
ney sweep test is carried out.
(20 - 80 °C)
2-14
Boiler
Boiler temperature for
chimney sweep mode
( 65)
65°
•
Supply temperature for enabling the chimney sweep
test
After this supply temperature is exceeded, the chimney
sweep test is enabled.
(20 - 80 °C)
2-15
Boiler
Comb.chamb.temp. for
chimney sweep mode
( 450)
450°
•
Combustion chamber temperature for enabling the
chimney sweep test
After this combustion chamber temperature is exceeded,
the chimney sweep test is enabled. (300 - 1000 °C)
2-16
Boiler
Frost protection
enable/disable
( 0)
0
•
Boiler frost protection
Switch the frost protection for the boiler on/off.
(0 / 1 )
Important - danger of frost!!!
2-17
Boiler
Antifreeze for pumps
if outside below
( 5)
5°
•
Frost protection for pumps
After the outside temperature falls under this value, the
pumps are automatically switched on.
(-30 - 10 °C)
2-18
Boiler
Antifreeze f.heating
if return below
( 2)
2°
•
Boiler frost protection
System switches on if return temperature falls below the
specified value.
(-5 - 40°C)
2-19
Boiler
Set temperature for
antifreeze
( 10)
10°
•
Preset boiler temperature for frost protection
Boiler target temperature if the frost protection places a
load on the system.
(0 - 50 °C)
No.
Display
Description
Table 6/4 - System level / 2 - Boiler