6 Using the heating system – Structure of the menus
128
6 - C
LEANING
5-04
Return
Set temperature
( 60)
60°C
•
Preset temperature of return flow
Set the temperature of the return flow.
(40 - 80 °C)
5-05
Return
Residual heat return
pump start at
( 150)
150s
•
Residual heat
Set the time for the return pump.
(0 - 600 s)
5-06
Return
PID return mix.valve
Amplification (P)
( 3.00)
3.00
•
Amplification factor for return flow mixer
5-07
Return
PID return mix.valve
Lag time (I)
(30.00)
30.00s
•
Lag time of the return flow mixer
5-08
Return
PID return mix.valve
Advance time (D)
( 10.0)
10.0s
•
Advance time of the return flow mixer
5-09
Resid. heat via
Acc. top
Acc. bottom
•
Use residual heat
Selection option for comparing the boiler temperature
for residual heat utilisation.
No.
Display
Description
Table 6/7 - System level / 5 - Return
No.
Display
Description
6-01
Tip grate
Off
On
•
Tip grate
Switching the automatic grate emptying function on or
off.
6-02
Cleaning
Operating hours
Stand-by
( 2)
2h
•
Tip grate
Number of heat generating operating hours after which
the grate empties upon being switched back on.
(0 - 50 h)
6-03
Cleaning
Operating hours
Continuous
operation
( 4)
4h
•
Tip grate
Number of operating hours after which the grate empties
during continuous operation of the system.
(0 - 50 h)
Table 6/8 - System level / 6 - Cleaning