6 Using the heating system – Structure of the menus
138
10-03
Heat circuit 1
Room set temperature
Day
( 22.0) 22.0°
•
Room set temperature daytime
Configure the room temperature for daytime operation.
(15.0 - 30.0 °C)
10-04
Heat circuit 1
Room set temperature
night
( 14.0) 14.0°
•
Room set temperature night
Configure the room temperature for night-time opera-
tion.
(10.0 - 25.0 °C)
10-05
Progr. 1 HC1
Mo Tu We Th Fr Sa Su
On 05:00 On 00:00
Off 22:00 Off 00:00
•
Heating times
Time block 1: Various enable times can be defined for the
individual days of the week.
✎
See page 104.
10-06
Progr. 2 HC1
Mo Tu We Th Fr Sa Su
On 00:00 On 00:00
Off 00:00 Off 00:00
•
Heating times
Time block 2: Various enable times can be defined for the
individual days of the week.
✎
See page 104.
10-07
Heat circuit 1
Outside temperature
Shut-down
( 20) 20°
•
The temperature outside
If the preset outside temperature is not met, the heating
circuit pump is turned off.
(0 - 50 °C)
10-08
Heat circuit 1
Room influencing fac-
tor
( 1.0) 1.0
•
Room influencing factor
The room influencing factor expresses how strongly any
deviation of the room temperature should affect the
temperature of supply water leaving the boiler. (0.1 - 5.0)
10-09
Heat circuit 1
Steepness
characteristic hea-
ting curve
( 1.6) 1.6
•
Characteristic heating curve
The steepness of the characteristic heating curve is used
to assign a certain supply temperature to a heating cir-
cuit, depending on the outside temperature. (0.5 - 3.5)
10-10
Thermostat HC1
no
yes
•
Indoor thermostat unit
Activate an indoor thermostat unit.
10-11
Heat circuit 1
Parallel shift
(0) 0°
•
Parallel shift of the characteristic heating curve
Set the parallel shift of the characteristic heating curve.
(0 - 20 °C)
No.
Display
Description
Table 6/12 - System level / 10 - Heating circuit 1