6 Using the heating system – Structure of the menus
124
4 - C
ONTROL
The default setting in the automatic mode of the heating system is
Combustion control
.
No.
Display
Description
4-01
Type of boiler control
Fixed value
Combustion ctrl.
Comb+output ctrl.
Log wood
•
Type of control for the combustion
"Fixed value" mode
“Combustion ctrl.” mode
“Combustion and output control” mode
“Log wood” emergency operation
4-02
Control
Fixed value
Dosage
( 20)
20%
•
Fuel quantity for “Fixed value” type of control
Option for setting a fixed fuel quantity for “Fixed value”
operation.
(0 - 100 %)
4-03
Control
Fixed value
Primary air
( 30)
30%
•
Primary air volume for “Fixed value” type of control
Option for setting a fixed primary air volume for “Fixed
value” operation.
(0 - 100 %)
4-04
Control
Fixed value
Secondary air
( 10)
10%
•
Secondary air volume for “Fixed value” type of control
Option for setting a fixed secondary air volume for “Fixed
value” operation. (0 - 100 %)
4-05
Control
Fixed value
Flue gas fan
( 30)
30%
•
Flue gas fan setting for “Fixed value”
Setting option for the speed of a flue gas fan for “Fixed
value” operation.
(0 - 100 %)
4-06
Control
Combustion control
Chamber set temp.
( 550)
550°C
•
Preset combustion chamber temperature for nominal
load
Set the target temperature for the combustion chamber
at nominal load.
Only possible for “Combustion control” mode.
(200 - 1000 °C)
4-07
Control
PID_1 comb.cham.temp
Amplification
(P)
( 7.0)
7.0
•
Amplification factor for combustion chamber tempe-
rature
For “Combustion and output control” mode.
4-08
Control
PID_1 comb.cham.temp
Lag time (I)
(300)
300s
•
Lag time of combustion chamber temperature
For “Combustion and output control” mode.
Table 6/6 - System level / 4 - Control