6 Using the heating system – Structure of the menus
125
4-09
Control
PID_1 comb.cham.temp
Advance time (D)
( 0.0)
0.0s
•
Advance time of combustion chamber temperature
For “Combustion and output control” mode.
4-11
Control
PID_1 comb.cham.temp
Minimum
( 300)
300°
•
Minimum combustion chamber temperature
For “Combustion and output control” mode.
4-12
Control
PID_1 comb.cham.temp
Maximum
( 550)
550°
•
Maximum combustion chamber temperature
For “Combustion and output control” mode.
4-13
Control
PID_2 Fuel
Amplification
(P)
( 0.04)
0.04
•
Amplification factor for fuel quantity
For “Combustion and output control” mode.
4-14
Control
PID_2 Fuel
Lag time (I)
(257.3)
257.3s
•
Lag time for fuel quantity
For “Combustion and output control” mode.
4-15
Control
PID_2 Fuel
Advance time (D)
( 0.0)
0.0s
•
Advance time for fuel quantity
For “Combustion and output control” mode.
4-17
Control
PID_2 Fuel
Minimum
( 10.0)
10.0%
•
Minimum fuel quantity
For “Combustion and output control” mode.
(0 - 100 %)
4-18
Control
PID_2 Fuel
Maximum
( 20.0)
20.0%
•
Maximum fuel quantity
For “Combustion and output control” mode.
(0 - 100 %)
4-20
Control
R-1 Primary air
at min fuel
( 30.0)
30%
•
Primary air volume for minimum fuel quantity
For “Combustion and output control” mode.
(0 - 100 %)
4-21
Control
R-1 Primary air
at max fuel
( 35.0)
35%
•
Primary air volume for maximum fuel quantity
For “Combustion and output control” mode.
(0 - 100 %)
No.
Display
Description
Table 6/6 - System level / 4 - Control