6 Using the heating system – Structure of the menus
127
5 - R
ETURN
4-33
Control
O2 fuel change
delta Minimum
( -10)
-10%
•
Fuel change due to residual oxygen
If the residual oxygen is too low, the specified percentage
value is deducted from the fuel quantity.
(-50 - -100 %)
4-34
Control
O2 fuel change
delta Maximum
( 10)
10%
•
Fuel change due to residual oxygen
If the residual oxygen is too low, the specified percentage
value is added to the fuel quantity.
(50 - 100 %)
4-35
Controller info
no
yes
•
Controller info
If set to “yes”, additional menu windows are displayed
with current controller values.
4-36
Control
Combustion
fan
speed
( 80)
80%
•
Input for combustion fan speed
(0 - 100%)
4-37
Control
Combustion
fan
speed Log wood
( 50)
50%
•
Input for combustion fan speed
For “Log wood” emergency operation.
(0 - 100%)
No.
Display
Description
Table 6/6 - System level / 4 - Control
Warning!
Falling below dew point
Do not set the return temperature below 60 °C.
No.
Display
Description
5-01
Return
Pumps on/off at
boiler temperature
( 57)
57°
•
Enabling of the return pump
If the boiler temperature is above this setting, the return
pump is enabled.
(40 - 80 °C)
5-02
Return
Mixing valve
total runtime
( 150)
150s
•
Total runtime of return flow mixer
Set the total runtime of the return flow mixing valve.
(100- 600 s)
5-03
Return
Mixing valve
Minimum
runtime
( 3)
3s
•
Minimum runtime of return flow mixer
Set the minimum runtime of the return flow mixing valve.
(1 - 100 s)
Table 6/7 - System level / 5 - Return