6 Using the heating system – Structure of the menus
112
I
NFORMATION
LEVEL
No.
Display
Description
i-01
Control
Combustion control
Boiler 80/75?
Return 60/60°C
•
Operating status
Configured control type
Boiler temperature set/actual
Return temperature set/actual
i-02
Control
Chamb.temp
550/540?
O2 7.0/6.9%
Fuel 70/70%
•
Operating status
Combustion chamber temp. set/actual
Residual oxygen set/actual
Fuel quantity set/actual
i-03
Control
Outside temp.
8/
8°C
Flue gas temp.
165°C
•
Heating required according to:
Outside temperature mean/current
Current flue gas temperature
i-04
Times
Control
01:29:36
•
Times
Currently running times of the operational states
i-05
Demand
External 0°C
Accumulator 80°C
•
Required preset boiler temperature
via an external contact
via accumulator
i-06
Demand HC ctrl.
HC1: 33°C
HC2: 45°C
HC3: 30°C
HC4: 32°C
HC5: 45°C
HC6: 31°C
•
Demand on the respective heating circuits
i-07
Demand DHW
DHW1:60°C DHW2:
60°C
•
Demand on the respective domestic hot water tanks
i-08
Boiler
Dosage 60%
Primary air
38%
Secondary air
52%
•
Boiler settings
Fuel quantity
Primary air setting
Secondary air setting
i-09
Boiler
Combust. air fan
100%
Ign. attempts
3/0
Flue gas fan
0/ 0%
•
Boiler settings
Combustion fan setting
Number of ignition attempts
Rpm flue gas fan
i-10
Mixer return
Mixer control
Return 60/60°C
Pump On
•
Return temperature control
Mixer operating status
Return temperature set/actual
Pump status (on/off)
Table 6/2 - Information level