4 Planning and installation – HDG Hydronic
76
See the hydraulic plan and the circuit diagram for the plug connec-
tions and the necessary sensors for your particular hydraulic system.
✎
The available hydraulic solution options can be found in the sec-
tion “4.10 HDG hydraulic systems” in this chapter or in the infor-
mation booklet “Hydraulic Solutions for the HDG Hydronic”.
Take great care that you use the correct sensors (contact sensors, im-
mersion sensors, outside temperature sensors) since, if incorrectly
applied, error messages and resulting malfunctions in the control
system could then occur.
All of the sensors in the HDG Hydronic are PT 1000 sensors.
I
NSTALLING
THE
OUTSIDE
TEMPERATURE
SENSOR
Temperature
PT 1000
Temperature
PT 1000
-50 °C
803.10 Ohm
25 °C
1097.40 Ohm
-40 °C
842.70 Ohm
30 °C
1116.70 Ohm
-30 °C
882.20 Ohm
40 °C
1155.40 Ohm
-20 °C
921.60 Ohm
50 °C
1194.00 Ohm
-10 °C
960.60 Ohm
60 °C
1232.40 Ohm
0 °C
1000.00 Ohm
70 °C
1270.70 Ohm
10 °C
1039.00 Ohm
100 °C
1385.00 Ohm
20 °C
1077.90 Ohm
150 °C
1573.10 Ohm
Table 4/7 - Characteristics of PT 1000
1.
Install the outside tempera-
ture sensor at the intended
position on the wall with its
cable outlet pointing down-
wards.
✎
See section “4.2 Connections”
in this chapter.
Figure 4/47 - Outside temperature sensor