Safety Relays
The safety relays specifications are described in the table:
Specifications
Details
Value
ZARB•H
ZARB•W
Number of contacts
The Base Station internally
implements 2 safety relays in
serial. Each safety relay has 2
contacts.
2
Logical type
-
NO
Insulation between Q0A and
Q0B
-
SELV insulation between (Q0A1, Q0A2)
and (Q0B1, Q0B2) for voltage up to
240 Vac
Q0A voltages
-
Up to 48 Vac
24...240 Vac
Q0B voltages
-
Q0A, Q0B
Maximum Ie current
24...240 Vac
-
4 A
6 A
Relay type according to
EN/IEC 60947-5-1
AC15
C300
B300
DC13
-
R300
Maximum making and
breaking capacities
(100.000 cycles)
AC15 / AC current according to
EN/IEC 60947-5-1
24 Vac
0.75 A
48 Vac
0.38 A
120 Vac
-
0.15 A
240 Vac
-
0.08 A
Inrush
450 VA
Maintained
45 VA
Maximum making and
breaking capacities
(100.000 cycles)
DC13 / DC current according to
EN/IEC 60947-5-1
24 Vdc
0.6 A
48 Vdc
0.3 A
120 Vdc
-
0.12 A
240 Vdc
-
0.06 A
Make
14.4 VA
Break
Minimum output current
The minimum current is
compatible with the STO
Schneider Electric drive input
impedance of 1.5 k
Ω
which
means a current of
24 V/1.5 k
Ω
= 16 mA.
10 mA / 24 Vdc
Содержание eXLhoist
Страница 12: ...12 EIO0000001505 12 2014...
Страница 34: ...Wireless Remote Control System 34 EIO0000001505 12 2014...
Страница 52: ...52 EIO0000001505 12 2014...
Страница 146: ...Using The Wireless Remote Control System 146 EIO0000001505 12 2014...
Страница 151: ...Diagnostic EIO0000001505 12 2014 151 Procedure to Leave the Diagnostic Mode Step Action 1 Power OFF the Remote Device...
Страница 177: ...eXLhoist Configuration Software EIO0000001505 12 2014 177 The diagram illustrates the use cases...
Страница 200: ...eXLhoist Configuration Software 200 EIO0000001505 12 2014...
Страница 213: ...EIO0000001505 12 2014 213 Harmony eXLhoist EIO0000001505 04 2014 Appendices...
Страница 214: ...214 EIO0000001505 12 2014...