Programming
Motor initial settings
2005-9015-009
01. August 2018
7.4.7
Motor capacity (HP)
Warning!
Improper setting of this parameter can cause injuries!
Attention!
Setting the ”MOTOR CAPACITY” beyond the value indicated by the
manufacturer causes heating, overload and damages to the motor.
Note!
To properly set the ”MOTOR CAPACITY” perform the fine tuning steps
as soon as the free stall or cross gutter cleaner is installed and
functional.
IVR PRO
● Press key until (ParA) appears;
key
● Press key to select;
● Press key until (P04) appears;
● Press key to select;
● Press keys to enter the motor capacity (HP) as per the value indicated on the
motor rating plate. Hold the button for fast change;
● Perform the fine tuning step.
IVR PRO Max@ccess
● Press ”SYSTEM”;
● Press ”MOTOR SETTINGS”;
● Use keypad arrows to select the parameter;
● Use the keypad to enter the motor capacity (HP) as per the value indicated on the motor
rating plate. When having a two motor drive unit, add both motor capacity ratings;
● Perform the fine tuning step.
Содержание Fit R-300
Страница 38: ...Geometric data 16 scraper 2005 9015 009 01 August 2018 38 168 5 8 16 scraper Floor mounted ...
Страница 40: ...Geometric data 16 scraper 2005 9015 009 01 August 2018 40 168 Guided by a groove ...
Страница 42: ...Geometric data V shape scraper 2005 9015 009 01 August 2018 42 168 5 9 V shape scraper Floor mounted ...
Страница 44: ...Geometric data V shape scraper 2005 9015 009 01 August 2018 44 168 Guided by a groove ...
Страница 46: ...Geometric data V shape scraper 2005 9015 009 01 August 2018 46 168 Bidirectional scraper ...
Страница 128: ...Programming Farm access 2005 9015 009 01 August 2018 128 168 7 21 3 Wiring 1 2 3 5 5 1 1 2 3 5 5 5 ...