Programming
Motor initial settings
2005-9015-009
01. August 2018
7.4.3
Amps
Note!
Improper setting of the ''AMPS'' parameter or an excessive load in front
the scraper(s) can trigger the A3 ''MAXIMUM LOAD EXCEEDED
(AMP)'' alarm.
IVR PRO
● Press key until (ParA) appears;
key
● Press key to select;
● Press key until (P07) appears;
● Press key to select;
● Press keys to enter the amperage as per the value indicated on the motor
rating plate. Hold the button for fast change.
IVR PRO Max@ccess
● Press ”SYSTEM”;
● Press ”MOTOR SETTINGS”;
● Use the keypad arrows to select the parameter;
● Use the keypad to enter the amperage as per the value indicated on the motor rating
plate (0.5 - 20.0).