2-26
L30 Line Current Differential System
GE Multilin
2.4 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.4.11 TYPE TESTS
L30 TYPE TESTS
2.4.12 PRODUCTION TESTS
THERMAL
Products go through an environmental test based upon an
Accepted Quality Level (AQL) sampling process.
TEST
REFERENCE STANDARD
TEST LEVEL
Dielectric voltage withstand
EN60255-5
2.2 kV
Impulse voltage withstand
EN60255-5
5 kV
Damped oscillatory
IEC61000-4-18 / IEC60255-22-1
2.5 kV CM, 1 kV DM
Electrostatic discharge
EN61000-4-2 / IEC60255-22-2
Level 3
RF immunity
EN61000-4-3 / IEC60255-22-3
Level 3
Fast transient disturbance
EN61000-4-4 / IEC60255-22-4
Class A and B
Surge immunity
EN61000-4-5 / IEC60255-22-5
Level 3 and 4
Conducted RF immunity
EN61000-4-6 / IEC60255-22-6
Level 3
Power frequency immunity
EN61000-4-7 / IEC60255-22-7
Class A and B
Voltage interruption and ripple DC
IEC60255-11
12% ripple, 200 ms interrupts
Radiated and conducted emissions
CISPR11 / CISPR22 / IEC60255-25
Class A
Sinusoidal vibration
IEC60255-21-1
Class 1
Shock and bump
IEC60255-21-2
Class 1
Seismic
IEC60255-21-3
Class 1
Power magnetic immunity
IEC61000-4-8
Level 5
Pulse magnetic immunity
IEC61000-4-9
Level 4
Damped magnetic immunity
IEC61000-4-10
Level 4
Voltage dip and interruption
IEC61000-4-11
0, 40, 70, 80% dips; 250 / 300 cycle interrupts
Damped oscillatory
IEC61000-4-12
2.5 kV CM, 1 kV DM
Conducted RF immunity, 0 to 150 kHz
IEC61000-4-16
Level 4
Voltage ripple
IEC61000-4-17
15% ripple
Ingress protection
IEC60529
IP40 front, IP10 back
Cold
IEC60068-2-1
–40°C for 16 hours
Hot
IEC60068-2-2
85°C for 16 hours
Humidity
IEC60068-2-30
6 days, variant 1
Damped oscillatory
IEEE/ANSI C37.90.1
2.5 kV, 1 MHz
RF immunity
IEEE/ANSI C37.90.2
20 V/m, 80 MHz to 1 GHz
Safety
UL508
e83849 NKCR
Safety
UL C22.2-14
e83849 NKCR7
Safety
UL1053
e83849 NKCR
Содержание L30
Страница 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 58: ...2 28 L30 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 126: ...4 30 L30 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...6 26 L30 Line Current Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 450: ...10 10 L30 Line Current Differential System GE Multilin 10 4 INSTANTANEOUS ELEMENTS 10 APPLICATION OF SETTINGS 10 ...
Страница 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 644: ...x L30 Line Current Differential System GE Multilin INDEX ...