
GE Multilin
L30 Line Current Differential System
6-5
6 ACTUAL VALUES
6.2 STATUS
6
The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact
output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of
the display indicates the logic state of the contact output.
For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn,
and VOn. For form-C contact outputs, the state is displayed as Off or On.
6.2.7 VIRTUAL OUTPUTS
PATH: ACTUAL VALUES
STATUS
VIRTUAL OUTPUTS
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic™ equation for that output.
6.2.8 AUTORECLOSE
PATH: ACTUAL VALUES
STATUS
AUTORECLOSE
AUTORECLOSE 1
The automatic reclosure shot count is shown here.
6.2.9 REMOTE DEVICES
a) STATUS
PATH: ACTUAL VALUES
STATUS
REMOTE DEVICES STATUS
The present state of the programmed remote devices is shown here. The
ALL REMOTE DEVICES ONLINE
message indicates
whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one required
remote device is not online.
VIRTUAL OUTPUTS
Virt Op 1
Off
Range: On, Off
MESSAGE
Virt Op 2
Off
Range: On, Off
MESSAGE
Virt Op 96
Off
Range: On, Off
AUTORECLOSE 1
AUTORECLOSE 1
SHOT COUNT:
0
Range: 0, 1, 2, 3, 4
REMOTE DEVICES
STATUS
All REMOTE DEVICES
ONLINE: No
Range: Yes, No
MESSAGE
REMOTE DEVICE 1
STATUS: Offline
Range: Online, Offline
MESSAGE
REMOTE DEVICE 2
STATUS: Offline
Range: Online, Offline
MESSAGE
REMOTE DEVICE 16
STATUS: Offline
Range: Online, Offline
NOTE
Содержание L30
Страница 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 58: ...2 28 L30 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 126: ...4 30 L30 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...6 26 L30 Line Current Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 450: ...10 10 L30 Line Current Differential System GE Multilin 10 4 INSTANTANEOUS ELEMENTS 10 APPLICATION OF SETTINGS 10 ...
Страница 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 644: ...x L30 Line Current Differential System GE Multilin INDEX ...