B-60
L30 Line Current Differential System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
C3E8
...Repeated for Virtual Output 88
C3F0
...Repeated for Virtual Output 89
C3F8
...Repeated for Virtual Output 90
C400
...Repeated for Virtual Output 91
C408
...Repeated for Virtual Output 92
C410
...Repeated for Virtual Output 93
C418
...Repeated for Virtual Output 94
C420
...Repeated for Virtual Output 95
C428
...Repeated for Virtual Output 96
Mandatory (Read/Write Setting)
C430
Test Mode Function
0 to 2
---
1
F245
0 (Disabled)
C431
Force VFD and LED
0 to 1
---
1
F126
0 (No)
C432
Test Mode Initiate
0 to 4294967295
---
1
F300
1
Clear commands (read/write)
C434
Clear All Relay Records Command
0 to 1
---
1
F126
0 (No)
Mandatory (Read Only)
C435
DSP Advanced Diagnostics Active
0 to 1
--
1
F126
0 (No)
C436
Synchrophasor Feature Active
0 to 1
--
1
F126
0 (No)
Mandatory (Read/Write Command)
C434
Relay Reboot Command
0 to 1
---
1
F126
0 (No)
C438
Save Volatile Data
0 to 1
---
1
F126
0 (No)
Clear Records (Read/Write Setting)
C450
Clear Fault Reports operand
0 to 4294967295
---
1
F300
0
C454
Clear Event Records operand
0 to 4294967295
---
1
F300
0
C456
Clear Oscillography operand
0 to 4294967295
---
1
F300
0
C458
Clear Data Logger operand
0 to 4294967295
---
1
F300
0
C45A
Clear Breaker 1 Arcing Current operand
0 to 4294967295
---
1
F300
0
C45C
Clear Breaker 2 Arcing Current operand
0 to 4294967295
---
1
F300
0
C45E
Clear Breaker 3 Arcing Current operand
0 to 4294967295
---
1
F300
0
C460
Clear Breaker 4 Arcing Current operand
0 to 4294967295
---
1
F300
0
C466
Clear Channel Status operand
0 to 4294967295
---
1
F300
0
C46C
Clear Unauthorized Access operand
0 to 4294967295
---
1
F300
0
C472
Reserved (13 items)
---
---
---
F001
0
Direct Input/Output Settings (Read/Write Setting)
C500
Direct Input Default States (8 items)
0 to 1
---
1
F108
0 (Off)
C508
Direct Input Default States (8 items)
0 to 1
---
1
F108
0 (Off)
C510
Direct Output x 1 Operand (8 items)
0 to 4294967295
---
1
F300
0
C520
Direct Output x 2 Operand (8 items)
0 to 4294967295
---
1
F300
0
Reset (Read/Write Setting)
C750
FlexLogic operand which initiates a reset
0 to 4294967295
---
1
F300
0
Control Pushbuttons (Read/Write Setting) (7 modules)
C760
Control Pushbutton 1 Function
0 to 1
---
1
F102
0 (Disabled)
C761
Control Pushbutton 1 Events
0 to 1
---
1
F102
0 (Disabled)
C762
...Repeated for Control Pushbutton 2
C764
...Repeated for Control Pushbutton 3
C766
...Repeated for Control Pushbutton 4
C768
...Repeated for Control Pushbutton 5
C76A
...Repeated for Control Pushbutton 6
C76C
...Repeated for Control Pushbutton 7
Force Contact Inputs/Outputs (Read/Write Settings)
C7A0
Force Contact Input
x
State (96 items)
0 to 2
---
1
F144
0 (Disabled)
C800
Force Contact Output
x
State (64 items)
0 to 3
---
1
F131
0 (Disabled)
87L Channel Tests (Read/Write)
C840
Local Loopback Function
0 to 1
---
1
F126
0 (No)
Table B–9: MODBUS MEMORY MAP (Sheet 52 of 61)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание L30
Страница 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 58: ...2 28 L30 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 126: ...4 30 L30 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...6 26 L30 Line Current Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 450: ...10 10 L30 Line Current Differential System GE Multilin 10 4 INSTANTANEOUS ELEMENTS 10 APPLICATION OF SETTINGS 10 ...
Страница 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...