B-52
L30 Line Current Differential System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
IEC 61850 GGIO4 analog input points configuration settings (read/write)
AF10
IEC 61850 GGIO4 analog input 1 value
---
---
---
F600
0
AF11
IEC 61850 GGIO4 analog input 1 deadband
0.001 to 100
%
0.001
F003
100000
AF13
IEC 61850 GGIO4 analog input 1 minimum
–1000000000000 to
1000000000000
---
0.001
F060
0
AF15
IEC 61850 GGIO4 analog input 1 maximum
–1000000000000 to
1000000000000
---
0.001
F060
1000000
AF17
...Repeated for IEC 61850 GGIO4 analog input 2
AF1E
...Repeated for IEC 61850 GGIO4 analog input 3
AF25
...Repeated for IEC 61850 GGIO4 analog input 4
AF2C
...Repeated for IEC 61850 GGIO4 analog input 5
AF33
...Repeated for IEC 61850 GGIO4 analog input 6
AF3A
...Repeated for IEC 61850 GGIO4 analog input 7
AF41
...Repeated for IEC 61850 GGIO4 analog input 8
AF48
...Repeated for IEC 61850 GGIO4 analog input 9
AF4F
...Repeated for IEC 61850 GGIO4 analog input 10
AF56
...Repeated for IEC 61850 GGIO4 analog input 11
AF5D
...Repeated for IEC 61850 GGIO4 analog input 12
AF64
...Repeated for IEC 61850 GGIO4 analog input 13
AF6B
...Repeated for IEC 61850 GGIO4 analog input 14
AF72
...Repeated for IEC 61850 GGIO4 analog input 15
AF79
...Repeated for IEC 61850 GGIO4 analog input 16
AF80
...Repeated for IEC 61850 GGIO4 analog input 17
AF87
...Repeated for IEC 61850 GGIO4 analog input 18
AF8E
...Repeated for IEC 61850 GGIO4 analog input 19
AF95
...Repeated for IEC 61850 GGIO4 analog input 20
AF9C
...Repeated for IEC 61850 GGIO4 analog input 21
AFA3
...Repeated for IEC 61850 GGIO4 analog input 22
AFAA
...Repeated for IEC 61850 GGIO4 analog input 23
AFB1
...Repeated for IEC 61850 GGIO4 analog input 24
AFB8
...Repeated for IEC 61850 GGIO4 analog input 25
AFBF
...Repeated for IEC 61850 GGIO4 analog input 26
AFC6
...Repeated for IEC 61850 GGIO4 analog input 27
AFCD
...Repeated for IEC 61850 GGIO4 analog input 28
AFD4
...Repeated for IEC 61850 GGIO4 analog input 29
AFDB
...Repeated for IEC 61850 GGIO4 analog input 30
AFE2
...Repeated for IEC 61850 GGIO4 analog input 31
AFE9
...Repeated for IEC 61850 GGIO4 analog input 32
IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting)
B01C
Default GOOSE/GSSE Update Time
1 to 60
s
1
F001
60
B01D
IEC 61850 GSSE Function (GsEna)
0 to 1
---
1
F102
1 (Enabled)
B013
IEC 61850 GSSE ID
---
---
---
F209
“GSSEOut”
B03F
IEC 61850 GOOSE Function (GoEna)
0 to 1
---
1
F102
0 (Disabled)
B040
IEC 61850 GSSE Destination MAC Address
---
---
---
F072
0
B043
IEC 61850 Standard GOOSE ID
---
---
---
F209
“GOOSEOut”
B064
IEC 61850 Standard GOOSE Destination MAC Address
---
---
---
F072
0
B067
IEC 61850 GOOSE VLAN Transmit Priority
0 to 7
---
1
F001
4
B068
IEC 61850 GOOSE VLAN ID
0 to 4095
---
1
F001
0
B069
IEC 61850 GOOSE ETYPE APPID
0 to 16383
---
1
F001
0
B06A
Reserved (2 items)
0 to 1
---
1
F001
0
IEC 61850 Server Configuration (Read/Write Settings/Commands)
B06C
TCP Port Number for the IEC 61850 / MMS Protocol
0 to 65535
---
1
F001
102
B06D
IEC 61850 Logical Device Name
---
---
---
F213
“IECName”
B07D
IEC 61850 Logical Device Instance
---
---
---
F213
“LDInst”
B08D
IEC 61850 LPHD Location
---
---
---
F204
“Location”
Table B–9: MODBUS MEMORY MAP (Sheet 44 of 61)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание L30
Страница 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 58: ...2 28 L30 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 126: ...4 30 L30 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...6 26 L30 Line Current Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 450: ...10 10 L30 Line Current Differential System GE Multilin 10 4 INSTANTANEOUS ELEMENTS 10 APPLICATION OF SETTINGS 10 ...
Страница 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 644: ...x L30 Line Current Differential System GE Multilin INDEX ...