5-116
L30 Line Current Differential System
GE Multilin
5.4 SYSTEM SETUP
5 SETTINGS
5
•
MSVCB 1 SVENA:
The SV Stream Control is set by either toggling an assigned Flexlogic operand or a remote client
write, to start and stop the streaming of R-SV frames: If remote client control is disabled, a negative response is pro-
vided to the client in response to a write attempt. A FlexLogic operand (SvEna) is provided for each Aggregator that
reflects the state of the SvEna control where “1”= Enabled and “0”=Disabled. The Logic for setting the SvEna control
bit is shown in the figure below.
Figure 5–47: LOGIC FOR SETTING SVENA CONTROL BIT
•
MSVCB 1 Client CONTRL:
This setting determines if a client can write to the reserve bit. If the assigned Flexlogic
operand is a logic 1 state, remote clients can write to both the reserve bit and the SvEna bit. If the Flexlogic operand is
a logic 0 state, the remote client writes to both the reserve bit and the SvEna will be rejected by the UR and a negative
response with the appropriate Service Error will be returned to the client.
•
MSVCB 1 SVENA Default:
This setting sets the default state of the stream (On or Off) on power-up or re-boot.
•
MSVCB 1 CONFREV:
The Configuration revision is incremented by the relay every time the configuration is changed.
This setting allows the user to reset the configuration back to 1 or a value from 1 to 4294967295.
•
MSVCB 1 PRIORITY:
A value from 0 through 7: The default value is 4.
•
MSVCB 1 IP Class:
The value represents the IPv4 Differentiated Services (formerly called TypeOfService) value. The
default value is set for Expedited Forwarding (101110B (46 or 2EH). This value provides priority routing – when sup-
ported in the routers.
•
MSVCB 1 VID:
A range of values limited from 0 to 4095.
•
MSVCB 1 APPID:
This setting allows the selection of a specific application ID for each sending device.
•
MSVCB 1 DEST IP Address:
This is the destination multicast address IP address which is entered in Standard IPV4
address format. The valid range for IPv4 is from 224.0.0.0 to 255.255.255.255 but the UR does not test the address
entered.
•
MSVCB 1 Security:
This setting selects what level of security and authentication is used, see table below, and is in the
form of an enumeration as per standard. The range is 1, 2 and 3.
Shaded settings in table below are not supported in firmware 7.0.
MESSAGE
MSVCB 1 DEST. IP:
224.0.0.0
Range: 0 to 255.255.255.255
Default: 224.0.0.0
MESSAGE
MSVCB 1 SECURITY:
0
Range: 0 to 2
Default: 0
ENUMERATION
AUTHENTICATION
ENCRYPTION
0
no
no
1
yes
no
2
yes
yes
NOTE
Содержание L30
Страница 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 58: ...2 28 L30 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 126: ...4 30 L30 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...6 26 L30 Line Current Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 450: ...10 10 L30 Line Current Differential System GE Multilin 10 4 INSTANTANEOUS ELEMENTS 10 APPLICATION OF SETTINGS 10 ...
Страница 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 644: ...x L30 Line Current Differential System GE Multilin INDEX ...