GE Multilin
L30 Line Current Differential System
5-87
5 SETTINGS
5.4 SYSTEM SETUP
5
•
SWITCH 1 OPEN:
This setting selects an operand that creates a programmable signal to operate an output relay to
open disconnect switch 1.
•
SWITCH 1 BLK OPEN
: This setting selects an operand that prevents opening of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
•
SWITCH 1 CLOSE:
This setting selects an operand that creates a programmable signal to operate an output relay to
close disconnect switch 1.
•
SWITCH 1 BLK CLOSE
: This setting selects an operand that prevents closing of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
•
SWTCH 1
A/3P CLSD:
This setting selects an operand, usually a contact input connected to a disconnect switch
auxiliary position tracking mechanism. This input should be a normally-open 52/a status input to create a logic 1 when
the disconnect switch is closed. If the
SWITCH 1 MODE
setting is selected as “3-Pole”, this setting selects a single input
as the operand used to track the disconnect switch open or closed position. If the mode is selected as “1-Pole”, the
input mentioned above is used to track phase A and the
SWITCH 1
B
and
SWITCH 1
C
settings select operands to
track phases B and C, respectively.
•
SWITCH 1
A/3P OPND:
This setting selects an operand, usually a contact input, that should be a normally-closed
52/b status input to create a logic 1 when the disconnect switch is open. If a separate 52/b contact input is not avail-
able, then the inverted
SWITCH 1 CLOSED
status signal can be used.
•
SWITCH 1
B CLOSED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B closed position as above for phase A.
•
SWITCH 1
B OPENED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B opened position as above for phase A.
•
SWITCH 1
C CLOSED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C closed position as above for phase A.
•
SWITCH 1
C OPENED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C opened position as above for phase A.
•
SWITCH 1 Toperate
: This setting specifies the required interval to overcome transient disagreement between the 52/a
and 52/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
expired, the
SWITCH 1 BAD STATUS
FlexLogic operand is asserted from alarm or blocking purposes.
•
SWITCH 1 ALARM DELAY:
This setting specifies the delay interval during which a disagreement of status among the
three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation
of the poles.
IEC 61850 functionality is permitted when the L30 is in “Programmed” mode and not in the local control mode.
NOTE
Содержание L30
Страница 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 58: ...2 28 L30 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 126: ...4 30 L30 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...6 26 L30 Line Current Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 450: ...10 10 L30 Line Current Differential System GE Multilin 10 4 INSTANTANEOUS ELEMENTS 10 APPLICATION OF SETTINGS 10 ...
Страница 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 644: ...x L30 Line Current Differential System GE Multilin INDEX ...