GE Multilin
L30 Line Current Differential System
B-31
APPENDIX B
B.4 MEMORY MAPPING
B
4446
User Programmable Battery Fail Function
0 to 1
---
1
F102
1 (Enabled)
4447
User Programmable SNTP Fail Function
0 to 1
---
1
F102
1 (Enabled)
4448
User Programmable IRIG-B Fail Function
0 to 1
---
1
F102
1 (Enabled)
444A
Process Bus Failure Operand
0 to 4294967295
---
1
F300
0
444C
PTP Fail Function
0 to 1
---
1
F102
1 (Enabled)
444D
User Programmable Third Ethernet Fail Function
0 to 1
---
1
F102
0 (Disabled)
444E
User Programmable SFP Fail Function
0 to 1
---
1
F102
0 (Disabled)
CT Settings (Read/Write Setting) (6 modules)
4480
Phase CT 1 Primary
1 to 65000
A
1
F001
1
4481
Phase CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
4482
Ground CT 1 Primary
1 to 65000
A
1
F001
1
4483
Ground CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
4484
...Repeated for CT Bank 2
4488
...Repeated for CT Bank 3
448C
...Repeated for CT Bank 4
4490
...Repeated for CT Bank 5
4494
...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (3 modules)
4500
Phase VT 1 Connection
0 to 1
---
1
F100
0 (Wye)
4501
Phase VT 1 Secondary
25 to 240
V
0.1
F001
664
4502
Phase VT 1 Ratio
1 to 24000
:1
1
F060
1
4504
Auxiliary VT 1 Connection
0 to 6
---
1
F166
1 (Vag)
4505
Auxiliary VT 1 Secondary
25 to 240
V
0.1
F001
664
4506
Auxiliary VT 1 Ratio
1 to 24000
:1
1
F060
1
4508
...Repeated for VT Bank 2
4510
...Repeated for VT Bank 3
4518
...Repeated for VT Bank 4
4520
...Repeated for VT Bank 5
4528
...Repeated for VT Bank 6
Source Settings (Read/Write Setting) (6 modules)
4580
Source 1 Name
0 to 1
---
---
F206
“SRC 1"
4583
Source 1 Phase CT
0 to 63
---
1
F400
0
4584
Source 1 Ground CT
0 to 63
---
1
F400
0
4585
Source 1 Phase VT
0 to 63
---
1
F400
0
4586
Source 1 Auxiliary VT
0 to 63
---
1
F400
0
4587
...Repeated for Source 2
458E
...Repeated for Source 3
4595
...Repeated for Source 4
459C
...Repeated for Source 5
45A3
...Repeated for Source 6
Power System (Read/Write Setting)
4600
Nominal Frequency
25 to 60
Hz
1
F001
60
4601
Phase Rotation
0 to 1
---
1
F106
0 (ABC)
4602
Frequency And Phase Reference
0 to 5
---
1
F167
0 (SRC 1)
4603
Frequency Tracking Function
0 to 1
---
1
F102
1 (Enabled)
87L Power System In-Zone Transformer (Read/Write Setting)
4606
In-Zone Transformer Connection
0 to 12
---
1
F560
0 (None)
4607
87L In-Zone Transformer Location
0 to 2
---
1
F562
0 (Local-Tap)
Breaker control (read/write settings)
47D0
Breaker 1 function
0 to 1
---
1
F102
0 (Disabled)
47D1
Breaker 1 name
---
---
---
F206
“Bkr 1"
47D4
Breaker 1 mode
0 to 1
---
1
F157
0 (3-Pole)
47D5
Breaker 1 open
0 to 4294967295
---
1
F300
0
47D7
Breaker 1 close
0 to 4294967295
---
1
F300
0
Table B–9: MODBUS MEMORY MAP (Sheet 23 of 61)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание L30
Страница 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 58: ...2 28 L30 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 126: ...4 30 L30 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...6 26 L30 Line Current Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 450: ...10 10 L30 Line Current Differential System GE Multilin 10 4 INSTANTANEOUS ELEMENTS 10 APPLICATION OF SETTINGS 10 ...
Страница 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 644: ...x L30 Line Current Differential System GE Multilin INDEX ...