5-64
L30 Line Current Differential System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
•
PUSHBTN 1 DROP-OUT TIME
: This setting applies only to “Self-Reset” mode and specifies the duration of the push-
button active status after the pushbutton has been released. When activated remotely, this setting specifies the entire
activation time of the pushbutton status; the length of time the operand remains on has no effect on the pulse duration.
This setting is required to set the duration of the pushbutton operating pulse.
•
PUSHBTN 1 LED CTL
: This setting assigns the FlexLogic operand serving to drive pushbutton LED. If this setting is
“Off”, then LED operation is directly linked to
PUSHBUTTON 1 ON
operand.
•
PUSHBTN 1 MESSAGE
: If pushbutton message is set to “High Priority”, the message programmed in the
PUSHBTN 1
ID
and
PUSHBTN 1 ON TEXT
settings will be displayed undisturbed as long as
PUSHBUTTON 1 ON
operand is asserted.
The high priority option is not applicable to the
PUSHBTN 1 OFF TEXT
setting.
This message can be temporary removed if any front panel keypad button is pressed. However, ten seconds of keypad
inactivity will restore the message if the
PUSHBUTTON 1 ON
operand is still active.
If the
PUSHBTN 1 MESSAGE
is set to “Normal”, the message programmed in the
PUSHBTN 1 ID
and
PUSHBTN 1 ON TEXT
settings will be displayed as long as
PUSHBUTTON 1 ON
operand is asserted, but not longer than time period specified
by
FLASH MESSAGE TIME
setting. After the flash time is expired, the default message or other active target message is
displayed. The instantaneous reset of the flash message will be executed if any relay front panel button is pressed or
any new target or message becomes active.
The
PUSHBTN 1 OFF TEXT
setting is linked to
PUSHBUTTON 1 OFF
operand and will be displayed in conjunction with
PUSHBTN 1 ID
only if pushbutton element is in the “Latched” mode. The
PUSHBTN 1 OFF TEXT
message will be displayed
as “Normal” if the
PUSHBTN 1 MESSAGE
setting is “High Priority” or “Normal”.
•
PUSHBUTTON 1 EVENTS
: If this setting is enabled, each pushbutton state change will be logged as an event into
event recorder.
Содержание L30
Страница 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 58: ...2 28 L30 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 126: ...4 30 L30 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...6 26 L30 Line Current Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 450: ...10 10 L30 Line Current Differential System GE Multilin 10 4 INSTANTANEOUS ELEMENTS 10 APPLICATION OF SETTINGS 10 ...
Страница 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 644: ...x L30 Line Current Differential System GE Multilin INDEX ...