4-63
02-15
Line-to-line Resistance of motor 1 Default: –
Range
【
1–60.000
】
Ω
02-17
Leakage Inductance Motor 1 Default: –
Range
【
0.01–200.00
】
mH
02-19
No-Load Voltage of motor 1 Default: –
Range
【
0.01–600.00
】
A
02-20
No-Load Current of motor 2 Default: –
Range
【
0.01–600.00
】
A
02-21
Rated current of motor 2 Default: –
Range
10%–200% of AC Drive rated current
02-22
Rated rotation speed of motor 2 Default: –
Range
【
0–60000
】
rpm
02-23
Rated voltage of motor 2 Default: 230.0 or 400.0
Range
240V:
【
50.0–240.0
】
V
480V:
【
100.0–480.0
】
V
02-24
Rated power of motor 2 Default: –
Range
【
0.01–600.00
】
KW
02-25
Rated frequency of motor 2 Default: 50.0/60.0
Range
【
4.8–599.0
】
Hz
02-26
Number of Motor Poles of Motor 2 Default: 4
Range
【
2–16
】
02-32
Line-to-line Resistance of motor 2 Default: –
Range
【
0.001–60.000
】
Ω
02-33
Proportion of Motor Leakage Inductance <1> Default: KVA
Range
【
0.1–15.0
】
%
02-15: Motor line-to-line resistance
Y-equivalent model of an induction motor
02-19: No-load motor voltage
Parameter determines the rated flux during motor’s rated rotation in SLV control mode. Set the value of this
parameter to the same value as parameter 17-08. A value of 10–50V below the input voltage level ensures that the
motor is capable of providing adequate torque performance when operating at nominal speed (or higher speed).
Setting the value too small can result in a reduction in no-load current, weakened motor flux and an increase in motor
current while the motor is loaded.