4-82
03-11=13
: Output is active when the output current > 03-15 for time specified in 03-16.
03-15
: Sets the output current detection level.
Function
Frequency Detection Function
Description
Output frequency
detection 1
ON
ON
OFF
OFF
03-14
03-14
03-13
03-13
03-13
03-13
time
time
Output
Frequency
Output
Frequency
Detection 1
Signal
Output is active when the output
frequency rises above the
frequency detection level
(03-13) + frequency detection
width (03-14) and deactivates
when the output frequency falls
below frequency detection level
(03-13).
Any of the digital outputs
function (03-11, 03-12 or 03-32)
can be set to 4 (Output
frequency detection 1).
Output frequency
detection 2
OFF
OFF
ON
ON
03-14
03-14
03-13
03-13
03-13
03-13
time
time
Output
Frequency
Output
Frequency
Detection 2
Signal
ON
Output is active when the output
frequency is below the
frequency detection level
(03-13) + frequency detection
width (03-14) and turns off when
the output frequency falls below
frequency detection level.
Any of the digital outputs
function (03-11, 03-12 or 03-32)
can be set to 5 (Output
frequency detection 2).
Frequency Output
DC Brake
DC Brake
ON
ON
OFF
OFF
Output
Frequency
Frequency
Output
Ing
OFF
OFF
OFF
OFF
OFF
ON
ON
Run
command
Base
Block
Output is active when the AC
Drive output frequency is
greater than 0.
03-15
Current Agree Level Default: 0.1
Range
【
0.1–999.9
】
A
03-16
Delay Time of Current Agree Detection Default: 0.1
Range
【
0.1–10.0
】
Sec