4-119
Fire Mode (Run-at-all-Costs Mode)
Warning
: Use of this mode for any application must be considered carefully and all safety implications must be taken
into account. When enabled and Fire Mode is activated (See multi-function digital inputs, 03-05=
【
28
】
), all
protection features of the AC Drive will be disabled and the unit will continue to operate until its possible destruction.
All liabilities for the use of this function will remain user’s responsibility.
08-48
Fire Mode Default: 0
Range
【
0
】
: Disabled
【
1
】
: Enabled
08-49
Fire Mode Multi-function Input Terminal Status Default: 0
Range
【
0
】
: Reset after Power Off
【
1
】
: Reset after Terminal Removed
08-50
Fire Mode Multi-function Terminal Status Default: 0000b
Range
【
xxx0b
】
: S6 A Contact
【
xxx1b
】
: S6 B Contact
08-51
Fire Mode Motor Speed Source Default: 0
Range
【
0
】
: Fire Mode Speed (08-52)
【
1
】
: PID Control
【
2
】
: AI2
08-52
Fire Mode Motor Speed Default: 100
Range
【
0.00–100.00
】
%
Note
:
Parameters 08-53 to 08-58 are only accessible after enabling Fire Mode in 08-48
08-53
Fire Mode PID Feedback Loss Detection Level Default: 0
Range
【
0–100
】
08-54
Fire Mode PID Feedback Loss Detection Time Default: 1.0
Range
【
0.0–10.0
】
08-55
Fire Mode PID Feedback Loss Detection Action Default: 1
Range
【
0
】
: Keep Running
【
1
】
: Fire Mode Speed (08-52)
【
2
】
: Max. Output Frequency of Motor 1 (01-02)
08-56
Fire Mode AI2 Signal Loss Detection Level Default: 80
Range
【
0–100
】
%
08-57
Fire Mode AI2 Signal Loss Detection Time Default: 1.0
Range
【
0.0–10.0
】
s
08-58
Fire Mode AI2 Signal Loss Detection Action Default: 1
Range
【
0
】
: Keep Running
【
1
】
: Fire Mode Speed (08-52)
【
2
】
: Max. Output Frequency (01-02)
08-59
Fire Mode Motor Direction Default: 0
Range
【
0
】
: Forward
【
1
】
: Reverse
08-60
Fire Mode Password Default: 00000
Range
【
00000–65534
】