3-9
3.8 Control Circuit Terminals and Jumpers
AO
24V
AI1
S6
S(+)
S(-)
10V
R2A
R2B
R1C
S1
S3
S5
AI2
R1A
SG
COM
S2
S4
SF1
R1B
AGND
Type
Terminal
Terminal function
Signal level
Digital
inputs
S1
Refer to parameter group 3 for more information and default
settings.
24 VDC, 8 mA, Optical
coupling isolation (Max,
voltage 30 VDC,
Input impedance 3.3kΩ)
High Logic: 13V
Low Logic: 10V
S2
S3
S4
S5
S6
Relay
outputs
R1A
NO (Normally
open)
Multi-function output: Run, Fault, setting
Frequency ,Frequency Reached, Auto Restart,
Momentary AC Power Loss, Rapid Stop ,Base
Block Stop Mode, Motor Overload Protection,
Drive Overload Protection, Over-torque Threshold
Level
、
Preset Current level Reached
、
Preset
Brake Frequency Reached, PID Feedback Signal
Loss, Final count value reached, Initial count value
reached, PLC Status Indicator ,PLC control…
250VAC/1A(30VDC/1A)
R1B
NC (Normally
closed)
R1C
COMMON
R2A
R2B
24VPower
supply
COM
Digital signal common terminal (JP1 Switching NPN position)
±15%,Max output current
60mA
24V
Digital signal common terminal (JP1 Switching PNP position)
Analog
inputs
10V
Built in Power for an external speed potentiometer
10V(Max current:20mA)
AI1/AV1
Multifunctional analog input: JP2 selects voltage or current input
0 – 10V,(Max current:20mA)
(Input impedance: 153KΩ)
Voltage: JP2 in AV1 position
Current: JP2 in AI1 position
AI2/AV2
Multifunctional analog input: JP3 selects voltage or current input
0 – 10V,0 –20mA
(Input impedance: 153KΩ)
Voltage: JP3 in AV2 position
Current: JP3 in AI2 position
AGND
The analog common terminal
----
Analog
output
AO
Multifunctional analog output terminal*3
0 –10V,(Max current:2mA)
AGND
Analog common terminal
----
Safety
switch
SF1,SF2 Terminal SF is a safety input and can be used to disable drive
externally. Note SF2 only available on ‘F’ version AC Drives.
----
SG
RS485
Comms.
S(+)
RS485+
----
S(-)
RS485-
• Multi-function analog output AO is for use of an analog output meter. Do not use this output for feedback
control.
• Control board’s 24V is to be used for internal control only, Do not use the internal power-supply to power
external devices.