4-84
RUN
STOP
ON
OFF
03-11=14
03-18
03-17
T
Hz
RUN
When 03-18≥03-17, the following sequence applies:
03-19
Relay (R1A-R2A) Type Default: 0000b
Range
xxx0b: R1 A contact xxx1b: R1 B contact
xx0xb: R2 A contact xx1xb: R2 B contact
Parameter 03-19 selects the digital output type between a normally open and a normally closed contact.
Example:
To have R1 normally open and R2 normally closed, set 03-19=xxx01.
Each bit of 03-19
represents an output:
03-19
=
0 0
0:
normally open contact
R2 R1
1:
normally closed contact
03-20
Internal / External Multi-function Input Terminal Default: 0
Range
【
0–63
】
03-21
Action to Set Internal Multi-function Input Terminals Default: 0
Range
【
0–63
】
03-22
Pre-set Count 1 Default: 0
Range
【
0–9999
】
03-23
Pre-set Count 2 Default: 0
Range
【
0–9999
】
03-24
Output Under Current Detection Default: 0
Range
【
0
】
: Invalid
【
1
】
: Valid
03-25
Output Under Current Detection Level Default: 0.1
Range
【
0–999.9
】
A
03-26
Output Under Current Detection Delay Time Default: 0.01
Range
【
0.0–655.35
】
Sec
03-27
UP/DOWN Frequency Hold/Adjust Selection Default: 0
Range
【
0
】
: Hold last set frequency when stopped
【
1
】
: Set frequency to 0 when stopped
【
2
】
: Allow speed changes from last set frequency when stopped
【
3
】
: Refresh frequency at acceleration