4-95
06- 00
Auto Run Mode Select Default: 0
Range
【
0
】
: Disabled
【
1
】
: Execute a single cycle operation. Restart speed is based on the previous stopped speed.
【
2
】
: Execute continuous cycle operation. Restart speed is based on the previous cycle stop speed.
【
3
】
: After completion of a single cycle, the on-going operation speed is based on the speed of the
last stage. Restart speed is based on the previous stopped speed.
【
4
】
: Execute a single cycle operation. Restart speed is based on the Speed-Stage 0.
【
5
】
: Execute continuous cycle operation. Restart speed is based on the Speed-Stage 0.
【
6
】
: After completion of a single cycle, the on-going operation speed is based on the speed of the
last stage. Restart speed is based on the Speed-Stage 0
06 Automatic Program Operation
Param. #
Parameter Name
Default
Range
06-01
Frequency setting speed-stage 1
5
【
0.00–599.00
】
Hz
06-02
Frequency setting speed-stage 2
10
06-03
Frequency setting speed-stage 3
20
06-04
Frequency setting speed-stage 4
30
06-05
Frequency setting speed-stage 5
40
06-06
Frequency setting speed-stage 6
50
06-07
Frequency setting speed-stage 7
50
06-08
Frequency setting speed-stage 8
5
06-09
Frequency setting speed-stage 9
5
06-10
Frequency setting speed-stage 10
5
06-11
Frequency setting speed-stage 11
5
06-12
Frequency setting speed-stage 12
5
06-13
Frequency setting speed-stage 13
5
06-14
Frequency setting speed-stage 14
5
06-15
Frequency setting speed-stage 15
5
06-16
Operation time setting speed-stage 0
0
【
0.0–6000.0
】
Sec
06-17
Operation time setting speed-stage 1
0
06-18
Operation time setting speed-stage 2
0
06-19
Operation time setting speed-stage 3
0
06-20
Operation time setting speed-stage 4
0
06-21
Operation time setting speed-stage 5
0
06-22
Operation time setting speed-stage 6
0
06-23
Operation time setting speed-stage 7
0
06-24
Operation time setting speed-stage 8
0
06-25
Operation time setting speed-stage 9
0
06-26
Operation time setting speed-stage 10
0
06-27
Operation time setting speed-stage 11
0
06-28
Operation time setting speed-stage 12
0
06-29
Operation time setting speed-stage 13
0
06-30
Operation time setting speed-stage 14
0
06-31
Operation time setting speed-stage 15
0
Note:
For parameters 06-01 to 06-16, if the maximum output frequency of motor is over 300Hz, the frequency resolution is
changed to 0.1Hz.