4-144
13-08
Restore factory setting / initialize Default: –
Range
【
1
】
: 2 wires initialization (50Hz) (220V/380V)
【
2
】
: 2 wires initialization (60Hz) (220V/380V)
【
3
】
: 2 wires initialization (50Hz) (230V/400V)
【
4
】
: 2 wires initialization (60Hz) (240V/480V)
【
5
】
: 2 wires initialization (50Hz) (220V/415V)
【
6
】
: 2 wires initialization (60Hz) (230V/400V)
【
7
】
: 2 wires initialization (50Hz) (220V/440V)
【
8
】
: 2 wires initialization (60Hz) (220V/440V)
【
1112
】
: PLC initialization (RESET)
Use parameter 13-08 to initialize the AC Drive to factory default. It is recommended to write down the modified
parameters before initializing the AC Drive. After initialization, the value of 13-08 will return to zero automatically
13-08=1: 2 Wire Initialization (220V/380V)
Multi-function digital input terminal S1 controls forward operation / stop command and S2 controls reverse operation /
stop command. AC Drive input voltage (01-14) is automatically set to 220V (240V class) or 380V (480V class). When
01-00 (V/F curve) = F, 01-02 will automatically be set to 50Hz.
13-08=2: 2 Wire initialization (220V/380V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation
/ stop command. AC Drive input voltage (01-14) is automatically set to 220V (240V class) or 380V (480V class).
When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=3: 2 Wire Initialization (230V/400V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation
/ stop command. AC Drive input voltage (01-14) is automatically set to 220V (240V class) or 400V (480V class).
When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.
13-08=4: 2 Wire Initialization (240V/480V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation
/ stop command. AC Drive input voltage (01-14) is automatically set to 220V (240V class) or 460V (480V class).
When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
Unlocking the AC Drive with key code (password)
Step
Key
Display
7. Press
READ/ENTER
key to edit
parameter
8. Display will show
indicating
a password is
set and AC Drive
is locked.
Note:
When the AC Drive is unlocked, the saved password is deleted. User must set a new password before re-locking the
AC Drive.
Step
Key
Display
8. Use the
navigation keys
to enter the
password we set
earlier (
).
11. Press
READ/ENTER
key to unlock
the AC Drive
Display will
flash