4-165
Note:
Only set parameter 22-04 or 22-06, the AC Drive will automatically calculate the other one.
Formula (22-04) = 120 x f (22-06) / Number of Poles (22-03)
22-05: PM motor maximum rotation speed
Set the maximum motor rated speed in rpm according to the motor nameplate.
22-06: PM motor rated frequency
Set the motor rated frequency according to the motor nameplate.
Only one of the two values is required, either PM motor rated speed (22-04) or PM motor rated frequency (22-06),
the AC Drive will automatically calculate the other upon entering the data based on the formula below:
120 x f (PM motor rated frequency
(PM motor rated speed) N
P (PM motor pole number)
)
22-10
PM SLV Start Current Default: 50
Range
【
20.0 – 120.0
】
% (Motor Rated Current)
22-11
I/F Mode Start Frequency Switching Point Default: 10
Range
【
1.0 – 20.0
】
%
22-14
Armature Resistance of PM Motor Default: 1
Range
【
0.001 – 30.000
】
Ω
22-15
D-axis Inductance of PM Motor Default: 10
Range
【
0.01 – 300.00
】
mH
22-16
Q-axis Inductance of PM Motor Default: 10
Range
【
0.01 – 300.00
】
mH
22-18
Flux-Weakening Limit Default: 0
Range
【
0 – 100
】
%
22-21
PM motor tuning Default: 0
Range
【
0
】
: PM Motor Tuning is not Active
【
1
】
: Parameter Auto-tune (for PMSLV Tuning)
22-22
PM motor tuning fault Default: 0
Range
【
0
】
: No Error
【
5
】
: Loop Adjustment Timed Out
【
7
】
: Other Motor Tuning Errors
【
9
】
: Current Abnormal during Loop Adjustment
22-23
PM SLV acceleration time Default: 1
Range
【
0.1–10.00
】
Sec
22-25
Initial position Detection of PM Motor Default: 1
Range
【
0
】
: Disable
【
1
】
: Detected when AC Drive is running
22-10: PMSLV Start Current
Set the torque current at start up as % of motor rated current.
22-11: I/F Mode Start Frequency Switching Point
Function for the switching from open-loop to closed-loop in PMSLV mode. The unit is percentage of rated speed of
the motor. It recommended to set this parameter to a value greater than 5% for 480V and a value greater than 10%
for 240V.
22-14: Armature Resistance of PM Motor
Set resistor for each phase of the motor in increments of 0.001Ω. Value is set automatically during motor tuning
(22-21).