Group 08 Protection Parameters
Param.
#
Parameter Name
Setting Range
Default
Unit
Control mode
Notes
V/F
SLV
PMSLV
08-36
PTC Input Filter Time
Constant
0.00 – 5.00
2
Sec
08-38
Delay Time Fan Off
0–600
60
Sec
08-39
Delay Time Motor
Overheat Protection
1–300
60
Sec
08-40
Motor2 Acceleration Stall
Prevention Level
1–100
HD: 150
%
X
X
ND: 120
08-41
Motor2 Acceleration Stall
Prevention Limit
1–100
50
%
X
X
08-42
PTC Protection Level
0.1–10.0V
0.7
V
08-43
PTC Restart Level
0.1–10.0V
0.3
V
08-44
PTC Warning Level
0.1–10.0V
0.5
V
08-46
Temperature Agree Level
0–254
0
°C
08-47
Temperature Reset Level
0–254
0
°C
08-48
Fire Mode
0: Disable
1: Enable
0
-
08-49
Fire Mode Multi-function
Input Terminal Status
0: Reset after Power Off
1: Reset after Terminal Removed
0
-
08-50
Input Terminal Type
xxx0b: S6 A Contact
xxx1b: S6 B Contact
0000b
-
08-51
Fire Mode Motor Speed
Source
0: Fire Mode Speed (08-52)
1: PID Control
2: AI2
0
-
08-52
Fire Mode Motor Speed
0.00–100.00
100.00
%
08-53
Fire Mode PID Feedback
Loss Detection Level
0–100
0
-
08-54
Fire Mode PID Feedback
Loss Detection Time
0.0–10.0
1.0
-
08-55
Fire Mode PID Feedback
Loss Detection Action
0: Keep Running
1: Fire Mode Speed (08–52)
2: Max. Output Frequency of Motor 1
(01-02)
1
-
08-56
Fire Mode AI2 Signal
Loss Detection Level
0–100
80
%
08-57
Fire Mode AI2 Signal
Loss Detection Time
0.0–10.0
1.0
s
08-58
Fire Mode AI2 Signal
Loss Detection Action
0: Keep Running
1: Fire Mode Speed (08-52)
2: Max. Output Frequency (01-02)
1
-
08-59
Fire Mode Motor
Direction
0: Forward
1: Reverse
0
-
08-60
Fire Mode Password
00000–65534
00000
-
08-53 to 08-58
: Only accessible after enabling Fire Mode in parameter 08-48.