4-71
03-0X =14
: Emergency stop (decelerate to zero and stop)
Refer to the "deceleration time of emergency stop" of parameter 00-26
Emergency stop switch wired to the S terminal that is set to 14 will trigger a deceleration to zero according to the
speed set in parameter 00-26 and then stop. Screen will display “ES”
03-0X =15
: External Baseblock Command (coast to stop)
When active the AC Drive output is turned off.
During run: When an external base block command is activated, the keypad displays "BBn BaseBlock (Sn)",
indicating the AC Drive output is turned off (n indicates the digital input number 1 – 6). Upon removing the base block
signal, the motor will run at the frequency reference. If speed search from frequency reference is active the AC Drive
output frequency starts from the frequency reference and searches for the coasting motor speed and continues to
operate. If speed search is not active the output frequency starts at 0Hz.
During deceleration: When an external base block command is activated, the keypad displays "BBn BaseBlock (Sn)",
indicating the AC Drive output is turned off (n indicates the digital input number 1 – 6). Upon removing the base block
signal, the motor is stopped or will coast to a stop and the AC Drive remains in the stop condition.
During acceleration: When an external base block command is activated, the keypad displays "BBn BaseBlock (Sn)",
indicating the AC Drive output is turned off (n indicates the digital input number 1 – 6). Upon removing the base block
signal, the motor will run at the frequency reference. If speed search from frequency reference is active the AC Drive
output frequency starts from the frequency reference and searches for the coasting motor speed and continues to
operate. If speed search is not active the output frequency starts at 0Hz.
Please refer to the figure below for external base block operation.
Run
Command
External
Baseblock
Output
Frequency
Speed search active
Coast to Stop
Coast to Stop
time
time
time
03-0X =16
: PID control disabled.
03-0X =17
: Fault reset
When the AC Drive trips on a fault the fault output contact is activated, the AC Drive output is turned off (base block)
and the keypad displays a dedicated fault message.
The following options are available to reset a fault:
1. Program one of the multi-function digital inputs (03-00 to 03-05) to 17 (reset fault) and activate input.*
2. Press the reset key of the digital operator (RESET).*
3. Cycle power to the AC Drive. Important Note: If a run command is active during power-up, the AC Drive will start
running automatically.
Note:
To reset an active fault the run command has to be removed.