4-75
03-0X =33
: DC braking
When input is active, DC-Injection braking is enabled during starting and stopping of the AC Drive.
DC Injection braking is disabled when a run or jog command is active. Refer to the DC braking time diagram below.
DC
injection
Brake
DC
injection
Brake
t
01-08
(Fmin)
Fout > 01-08 (Fmin)
Fout > 07-06 (DC-Inj Start Freq.)
Run Or Jog
Command
DC injection
Braking
Command
Output
Frequency
OFF
ON
OFF
ON
t
t
07-06
(Fdc-inj)
03-0X =34
: Speed Search
Activate speed search function
03-0X =40
: Motor 2 Selection
Motor 1 or motor 2 can be selected via the digital input. This function is only available in V/F control mode.
03-0X =47
: Fire mode
Fire Mode must first be enabled with parameter 08-48. When input is active disables all AC Drive warning and
hardware protections. This function is commonly used in commercial applications where the AC Drive controls an
exhaust fan and needs run to destruction in case of a fire.
03-0X =48
: KEB acceleration
When input is active enables KEB (Kinetic Energy Braking) to accelerate back to the preset frequency after braking.
Refer to the parameter description of 11-47 and 11-48 for more details on KEB.
Note:
Parameter 11-47 to a value greater than 0 before setting 03-0X=48.
03-0X =65
: Short Circuit braking
When active stops AC Drive by turning on Short-circuit braking. Short-circuit braking is disabled when a run or jog
command is active.
t
01-08
(Fmin)
The large of 01-08
or 07-07
OFF
ON
OFF
ON
t
t
Run Command
or
Jog Command
Short Circuit
Braking
Command
Output
Frequency
Short
Circuit
Brake
Short
Circuit
Brake