4-10
Group 00 Basic Parameters
Param.
#
Parameter Name
Setting Range
Default
Unit
Control Mode
Notes
V/F
SLV
PM/SLV
00-13
Frequency Lower Limit
0.00-599.99
0
Hz
(Note)
00-14
Acceleration Time 1
0.1–6000.0
KVA
s
*1
00-15
Deceleration Time 1
0.1–6000.0
KVA
s
*1
00-16
Acceleration Time 2
0.1–6000.0
KVA
s
*1
00-17
Deceleration Time 2
0.1–6000.0
KVA
s
*1
00-18
Jog Frequency
1.00–25.00
2
Hz
*1*7
00-19
Jog Acceleration Time
0.1–25.5
KVA
s
*1*7
00-20
Jog Deceleration Time
0.1–25.5
KVA
s
*1*7
00-21
Acceleration Time 3
0.1–6000.0
KVA
s
*1
00-22
Deceleration Time 3
0.1–6000.0
KVA
s
*1
00-23
Acceleration Time 4
0.1–6000.0
KVA
s
*1
00-24
Deceleration Time 4
0.1–6000.0
KVA
s
*1
00-26
Emergency Stop Time
0.1–3600.0
5
s
00-27
HD/ND Mode
(F5/F6 Only)
0: HD (Constant Torque)
0
-
X
X
(Note)
1: ND (Variable Torque)
00-34
Language (For external
LCD keypad only)
0: English
0
-
1: Simplified Chinese
2: Traditional Chinese
3: Turkish
00-35
Minimum Frequency
Detection
0: Alarm
0
-
1: Keep Running At Lower Frequency
00-36
PID Lower Frequency
Selection
0: Lower Frequency of PID Sleep Mode
(disable)
0
-
1: 0Hz of PID Sleep Mode (enable)
00-11:
Initial Frequency Setpoint range depends on the setting of 01-02 and 01-08 or 01-16 and 01-22 for V/F and SLV
modes. Depends on 22-06 for PMSLV mode.
00-12:
Frequency upper limit range depends on the setting of 01-02 or 01-16 for V/F and SLV modes. Depends on 22-06 for
PMSLV mode.
00-13:
Frequency lower limit range depends on the setting of 01-08 or 01-22 for V/F and SLV modes. Depends on 22-06 for
PMSLV mode.
00-27:
If parameter 00-27 is set to ND mode, group 02 motor 1 parameter will automatically be adjusted.
If parameter 00-27 is set to HD mode, group 02 motor 1 parameter will automatically be adjusted.
It is recommended that parameter 00-27 be set first before performing an auto-tune because motor parameters will
be updated automatically.
Applicable to Frames 5 and 6 only.
*1:
Parameter can be changed while running.
*3:
Parameter will not reset to default during a factory reset (initialization).
*4:
Read-only Parameter
*7: