4-22
Group 07 Start/Stop Parameters
Param.
#
Parameter Name
Setting Range
Default
Unit
Control mode
Notes
V/F
SLV
PMSLV
07-25
Low Voltage Detection
Time
0.00–1.00
0.02
Sec
07-26
SLV Coast to Stop
Start-up Mode Selection
0: Start With Speed Search
1: Normal Start
0
-
X
X
07-27
Start after Fault During
SLV Mode
0: Start With Speed Search
1: Normal Start
0
-
X
X
07-28
Start after External
BaseBlock
0: Start With Speed Search
1: Normal Start
0
-
X
07-29
Run Command at Action
of DC Braking
0: Not Allowable to Run
1: Allowable to Run
0
-
X
X
07-33
Speed Search Start
Frequency
0: Maximum Output Frequency
1: Frequency Command
0
-
X
07-34
Start Short-Circuit
Braking Time
0.00–100.00
0
Sec
X
X
07-35
Stop Short-Circuit
Braking Time
0.00–100.00
0.5
Sec
X
X
07-36
Short-Circuit Braking
Current Limited
0.0–200.0
100
%
X
X
07-37
Pre-Excitation Time
0.00–10.00
2
Sec
X
X
07-38
Pre-Excitation Level
50–200
100
%
X
X
07-39
PM Motor Speed Search
Function Short-Circuit
Braking Time
0.00–100.00
0
Sec
X
X
07-40
PM Motor Speed Search
Function DC Injection
Braking Time
0.00–100.00
0
Sec
X
X
07-45
Terminal Stop Display
0: Enabled
1: Disabled
0
-
Group 08 Protection Parameters
Param.
#
Parameter Name
Setting Range
Default
Unit
Control mode
Notes
V/F
SLV
PMSLV
08-00
Stall Prevention
Function
xxx0b: Stall prevention is enabled in
acceleration.
xxx1b: Stall prevention is disabled in
acceleration.
xx0xb: Stall prevention is enabled in
deceleration.
xx1xb: Stall prevention is disabled in
deceleration.
x0xxb: Stall prevention is enabled in
operation
x1xxb: Stall prevention is disabled in
operation
0xxxb: Stall prevention in operation is
based on deceleration time of speed-
stage 1.
1xxxb: Stall prevention in operation is
based on deceleration time of speed-
stage 2.
0000b
-
08-01
Stall Prevention Level
During Acceleration
20–200
HD: 150
%
ND: 120
08-02
Stall Prevention Level
During Deceleration
240V: 330V–410V
385V
V
480V: 660V–820V
770V
08-03
Stall Prevention Level
During Run
30–200
HD: 160
%
X
X
ND: 120