13-08=5: 2 Wire Initialization (220V /415V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation
/ stop command. AC Drive input voltage (01-14) is automatically set to 220V (220V class) or 415V (440V class).
When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.
13-08=6: 2 Wire Initialization (230V/400V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation
/ stop command. AC Drive input voltage (01-14) is automatically set to 230V (220V class) or 400V (440V class).
When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=7: 2 Wire Initialization (220V/440V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation
/ stop command. AC Drive input voltage (01-14) is automatically set to 220V (220V class) or 440V (440V class).
When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.
13-08=8: 2 Wire Initialization (220V/440V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation
/ stop command. AC Drive input voltage (01-14) is automatically set to 220V (220V class) or 440V (440V class).
When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=1112: PLC Initialization
Clear built-in PLC ladder logic and related values.
The following parameters are not affected parameter 13-08 Restore to Factory / Initialization
Number
Parameters
00-00
Control Mode Selection
00-34
Language
00-27
HD/ND Mode Selection
01-00
V/F Curve Selection
01-26
V/F Curve of Motor 2
13-00
AC Drive Capacity Selection
13-03
Cumulative Operation Hours 1
13-04
Cumulative Operation Hours 2
13-05
Cumulative Operation Time
13-10
Parameter Password Function 2 Default: 0
Range
Read-only
13-51
Hour Meter Reset Default: 0
Range
【
0
】
: Do not clear Cumulative Operation Hours
【
1
】
: Clear Cumulative Operation Hours
14 PLC Parameters
Param. #
Parameter Name
Default
Range
14-00
T1 set value 1
0
【
0–9999
】
14-01
T1 set value 2 (mode 7)
0
14-02
T2 set value 1
0
14-03
T2 set value 2 (mode 7)
0
14-04
T3 set value 1
0
14-05
T3 set value 2 (mode 7)
0
14-06
T4 set value 1
0