4-67
Value
Function
Description
Control Mode
Name
LCD Display
V/F
SLV PM/SLV
16
PID control disabled
PID Disable
ON: PID control disabled
O
O
O
17
Fault reset (Reset)
Fault Reset
ON: Fault reset
O
O
O
18
Auto Run Mode Enable
ON: Auto run mode enabled (06-00)
-
-
-
19
Speed Search
Speed Search 1
ON: Speed search from the
maximum output frequency
O
O
X
20
Energy Saving
Energy saving
ON: Manual energy saving control
is based on the settings of 11-
12 and 11-18.
O
X
X
21
Reset PID Integral Value
to Zero
PID I-Reset
ON: PID integral reset
O
O
O
22
Counter Input
Cnt Input
ON: Counter input by digital input
O
O
O
23
Counter Reset
Cnt Reset
ON: Counter reset by digital input
O
O
O
24
PLC Input
PLC Input
ON: PLC input
O
O
O
25
Pulse Width Measurement
(S3)
Pulse Input-Width
Measure
ON: Switch to pulse width
measurement
O
O
O
26
Pulse frequency
Measurement (S3)
Pulse Input-Freq.
Measure
ON: Switch to pulse frequency
measurement
O
O
O
27
Local/Remote Selection
Local/Remote
ON: Local mode (via the digital
operator)
OFF: Frequency and operation
command will be determined
according to the setting of
parameter (00-02 and 00-05).
O
O
O
28
Remote Mode Selection
Remote Mode Sel
ON: RS-485 communication control
active
OFF: Control circuit terminal active
O
O
O
29
Jog Frequency Selection
JOG Freq sel
ON: Jog Frequency Active
O
O
O
33
DC Braking
DC Brake
Command
ON: DC braking active
O
O
O
34
Speed Search 2 (From
Frequency Command)
Speed Search 2
ON: Speed search from set
frequency
O
O
X
40
Motor 1/Motor 2 Selection Motor 2 Switch
ON: Select motor 2
O
O
X
47
Fire Mode (Forced
Operation Mode)
Fire Mode
ON: Fire Mode Active (disables
hardware and software fault
/alarm protection and runs AC
Drive at 08-17 frequency).
O
O
O
48
KEB Acceleration
KEB Accel.
ON:KEB acceleration start enabled
O
O
O
65
Short-Circuit Breaking
SC Brk
ON: Short-Circuit Braking active
X
X
O
66
PID Control Disable 2
PID Disable
ON: PID control disabled
O
O
O
68
External Fault
Ext. Fault
ON: External Fault Alarm
O
O
O
69
External Overload
ON: External Overload Alarm
O
O
O
03-0X =00
: 2-wire control forward operation. For more information, see parameter 00-04 details.
03-0X =01
: 2-wire control reverse operation. For more information, see parameter 00-04 details.