4-93
Maximum output frequency:
Parameter 01-00=F, maximum output frequency set by 01-02, 01-00 ≠ F, maximum output frequency determined by
V/F curve selected (50.0 / 60.0 / 90.0 / 120.0 / 180.0).
Example
: 01-00=0 (50Hz (maximum output frequency), 05-02=10 Hz (multi-step speed 0), 05-17=5.0s (Acceleration
time), 05-18=20.0 sec. (Deceleration time).
Acceleration time calculation formula
5.0 x 10 Hz
Time it takes to reach set frequency =
= 1.0 sec.
50 Hz
Deceleration time calculation formula
20.0 x 10 Hz
Time it takes to reach set frequency =
= 4.0 sec.
50 Hz
Example
: Acceleration / deceleration timing when 05-00 is set to 1. In this example the following parameters are set:
00-02=
【
1
】
(External Terminal Operation)
00-04=
【
1
】
(Operation Mode: Run/Stop-Forward/Reverse).
03-00=
【
0
】
(Terminal S1: Run /Stop)
03-01=
【
1
】
(Terminal S2: Reversal /Stop)
03-02=
【
2
】
(Terminal S3: Preset Speed 1)
03-03=
【
3
】
(Terminal S4: Preset Speed 2)
03-03=
【
4
】
(Terminal S5: Preset Speed 3)
If the run command is cycled on and off, acceleration and deceleration time (a – f) is calculated based on the active
speed command as follows:
Terminal S1
Terminal S2
Terminal S3
Terminal S4
Run
Run
Run
Stop
Stop
Stop
Off
Off
Off
Off
On
On
a
b
c
d
e
f
P
res
et
Speed
0
Preset
Speed
1
Preset
Speed
2
05-01
05-02
05-03
T
Hz
in sec.
(05-17) x (05-01)
(05-18) x (05-01)
(05-19) x (05-02)
(01-02)
(01-02)
(01-02)
a =
b =
c =
(05-20) x (05-02)
(05-21) x (05-02)
(05-22) x (05-03)
(01-02)
(01-02)
(01-02)
d =
e =
f =
in sec.