7-10
LED Display
Description
Cause
Possible Solutions
Fire Mode
Enabled
Fire mode enabled
● Fire mode enabled.
● Check for cause of fire
mode activation. If it is OK
to deactivate fire mode,
turn the power off and on
again.
Parameter
Setting Error
Parameter setting error.
● The parameter setting is
incorrect.
● Please refer to parameter
listing and details for
correct settings
Direct Start
Warning
The AC Drive can’t start
directly, due to 07-04=1
● Run command from the
terminal is enabled and
07-04=1
● Remove the run command
from the terminal first, and
enable later.
External
Terminal
Stop Error
External Terminal is main run
command source selection
(00-02=1) and run command
executes but executes stop
command from keypad.
● Run command executes from
external terminal but executes
stop command from keypad.
● Remove the run command
from external terminal
Voltage on
C/B Error
Control board voltage error.
● Error detecting voltages
● Too much noise
● Control board failure
● Check the voltage on the
control board.
EEPROM
Save Error
The data saved in EEPROM
is wrong.
● EEPROM circuit failure.
● Parameter check error after
power on.
● Restore factory setting,
then power off and on
again.
If warning reoccurs,
replace control board.
Control Board
Error
Firmware can’t write to
Control board.
● Firmware not compatible with
Control board.
● Replace the control board.