Lift-off minimum voltage
9.0 VDC
Device capacitance / inductance
Class (Basic or Link Master)
Link Master (LAS)
Number of available VCRs
Maximum 20, including one fixed
Links
Maximum 40
Minimum slot time / maximum response delay/ minimum intermessage delay
8/5/8
Blocks and Execution time
Table A-1: Execution Time
Block
Execution time
1 Resource block
N/A
5 Transducer blocks (Level, Register, Adv_Config, Volume, and LPG)
N/A
6 Analog Input (AI)
10 ms
2 Analog Output (AO)
10 ms
1 Proportional/Integral/Derivate (PID)
15 ms
1 Signal Characterizer (SGCR)
10 ms
1 Integrator (INT)
10 ms
1 Arithmetic (ARTH)
10 ms
1 Input Selector (ISEL)
10 ms
1 Control Selector (CS)
10 ms
1 Output Splitter (OS)
10 ms
For more information, see the F
OUNDATION
Fieldbus Blocks
.
Instantiation
Yes
Conforming F
OUNDATION
Fieldbus
ITK 6
Field Diagnostics support
Yes
Reference Manual
Specifications and reference data
00809-0100-5900
September 2019
Rosemount 5900S Radar Level Gauge
225
Содержание Rosemount 5900S Series
Страница 1: ...Reference Manual 00809 0100 5900 Rev EA September 2019 Rosemount 5900S Radar Level Gauge ...
Страница 6: ...Contents Reference Manual September 2019 00809 0100 5900 vi Reference Manual ...
Страница 12: ...Introduction Reference Manual September 2019 00809 0100 5900 12 Reference Manual ...
Страница 182: ...Configuration Reference Manual September 2019 00809 0100 5900 182 Reference Manual ...
Страница 186: ...Operation Reference Manual September 2019 00809 0100 5900 186 Reference Manual ...
Страница 222: ...Service and troubleshooting Reference Manual September 2019 00809 0100 5900 222 Reference Manual ...
Страница 266: ...Product Certifications Reference Manual September 2019 00809 0100 5900 266 Reference Manual ...