Echo peaks
The
Echo Peaks
window lets you register false echoes. You may also point out which peak is
the actual product surface. This function may be useful to facilitate surface echo tracking
in a tank with many disturbing objects.
When using this function you should check that registered echoes correspond to actual
objects in the tank.
Figure 4-24: False Echo Registration
Reference Manual
Configuration
00809-0100-5900
September 2019
Rosemount 5900S Radar Level Gauge
167