Write protection using TankMaster
™
A Rosemount 5900S can be software write protected to avoid unintentional configuration
changes. Software write protection locks the holding register database.
Procedure
1. Start the Rosemount TankMaster WinSetup program.
2. In the
TankMaster WinSetup
workspace, select the
Logical View
tab.
3. Right-click the device icon.
4. Select
Write Protect
.
5. In the
New State
drop-down list, select
Protected
, and then click the
Apply
button
to save the new write protect state.
Now the holding register database is locked. As long as the device is write protected
no configuration changes can be made.
6. Click the
OK
button to close the
Write Protect
window.