4.10.2
Block instantiation
The Rosemount 5900S supports the use of function block instantiation. Then the number
of blocks and block types can be defined to match specific application needs. The number
of blocks that can be instantiated is only limited by the amount of memory within the
device and the block types that are supported by the device. Instantiation does not apply
to standard device blocks like the Resource and transducer blocks.
By reading the parameter “FREE_SPACE” in the Resource block you can determine how
many blocks you can instantiate. Each block that you instantiate takes up 4.6% of the
“FREE_SPACE”.
Block instantiation is done by the host control system or configuration tool, but not all
hosts implement this functionality. Please refer to your specific host or configuration tool
manual for more information.
4.10.3
Factory configuration
The following fixed configuration of function blocks is provided:
Table 4-4: Function Blocks for the Rosemount 5900S
Function Block
Index
Default Tag
Available
1600
AI 1600
Fixed
Analog Input
1700
AI 1700
Fixed
Analog Input
1800
AI 1800
Fixed
Analog Input
1900
AI 1900
Fixed
Analog Input
2000
AI 2000
Fixed
Analog Input
2100
AI 2100
Fixed
Analog Output
2200
AO 2200
Default, deletable
Analog Output
2300
AO 2300
Default, deletable
PID
2400
PID 2400
Default, deletable
Control Selector
2500
CSEL 2500
Default, deletable
Output Splitter
2600
OSPL 2600
Default, deletable
Signal Characterizer
2700
CHAR 2700
Default, deletable
Integrator
2800
INTEG 2800
Default, deletable
Arithmetic
2900
ARITH 2900
Default, deletable
Input Selector
3000
ISEL 3000
Default, deletable
(1)
See
for more information.
(2)
See
Reference Manual
Configuration
00809-0100-5900
September 2019
Rosemount 5900S Radar Level Gauge
139
Содержание Rosemount 5900S Series
Страница 1: ...Reference Manual 00809 0100 5900 Rev EA September 2019 Rosemount 5900S Radar Level Gauge ...
Страница 6: ...Contents Reference Manual September 2019 00809 0100 5900 vi Reference Manual ...
Страница 12: ...Introduction Reference Manual September 2019 00809 0100 5900 12 Reference Manual ...
Страница 182: ...Configuration Reference Manual September 2019 00809 0100 5900 182 Reference Manual ...
Страница 186: ...Operation Reference Manual September 2019 00809 0100 5900 186 Reference Manual ...
Страница 222: ...Service and troubleshooting Reference Manual September 2019 00809 0100 5900 222 Reference Manual ...
Страница 266: ...Product Certifications Reference Manual September 2019 00809 0100 5900 266 Reference Manual ...