Figure 3-28: Terminal Compartment 2-in-1 Version
$
'
(
)%
)%
)%
)%
)%
)%
$
)%
)%
%
%
&
A.
Test terminals
B.
Ground terminals, internal
C.
Jumpers between X3 and X4
D.
Two tankbuses
E.
Single tankbus
FB.
Field Bus
When using two separate tankbuses, connect X1 to Tankbus 1 and X4 to Tankbus 2.
Connect to X1 when using a single tankbus, and jumpers between X3 and X4.
Table 3-11: Terminal Block Connections for the Rosemount 5900S with Two
Tankbuses
Connection
Two-in-One / Two tankbuses
X1: Primary Tankbus in Intrinsically safe Tankbus input for level gauge 1, power and
communication
X2: Primary Terminate
on
Termination for primary tankbus. The integrated line terminator is
connected over the Tankbus when a jumper is placed in the terminal
block.
X3: Primary Tankbus
out
Primary Tankbus output connected to X1 for optional daisy-chain
connection to other devices
X4: Secondary Tankbus
in
Intrinsically safe Tankbus input for level gauge 2, power and
communication
Test terminals
Test terminals for temporary connection of a field communicator
Installation
Reference Manual
September 2019
00809-0100-5900
88
Reference Manual
Содержание Rosemount 5900S Series
Страница 1: ...Reference Manual 00809 0100 5900 Rev EA September 2019 Rosemount 5900S Radar Level Gauge ...
Страница 6: ...Contents Reference Manual September 2019 00809 0100 5900 vi Reference Manual ...
Страница 12: ...Introduction Reference Manual September 2019 00809 0100 5900 12 Reference Manual ...
Страница 182: ...Configuration Reference Manual September 2019 00809 0100 5900 182 Reference Manual ...
Страница 186: ...Operation Reference Manual September 2019 00809 0100 5900 186 Reference Manual ...
Страница 222: ...Service and troubleshooting Reference Manual September 2019 00809 0100 5900 222 Reference Manual ...
Страница 266: ...Product Certifications Reference Manual September 2019 00809 0100 5900 266 Reference Manual ...