apply for cable inlets and outlets (or plugs). Cables must be properly attached to the
cable glands.
Figure 3-23: Terminal Compartment
$
$
%
'
(
&
)
A. Cable glands
B. Internal Ground screws
C. Terminals for signal and power supply
D. Locking screw (Unscrew to lock)
E. External Ground screw
F. Cover
Conductor recommendations
Ensure that you use cables suitable for the terminal block of the Rosemount 5900S. The
terminal block is designed for cables that meet the specifications as illustrated below.
Figure 3-24: Conductor and Insulation Requirements
$
%
&
A. Conductor insulation. Maximum diameter Ø: 2.9 mm.
B. Stripping length: 8 to 9 mm.
C. Conductor cross-sectional area, see
Installation
Reference Manual
September 2019
00809-0100-5900