3. Choose the
All
option and type
65510
in the
Start Register
input field.
4. Type the desired number of registers to be displayed in the
Number of Registers
field and click the
Read
button.
5. Double-click in the
Value
(65535) field.
6. From the drop-down list, select the
Reset_to _factory_setting
option.
7. Click the
OK
button.
Service and troubleshooting
Reference Manual
September 2019
00809-0100-5900
202
Reference Manual