6.2
Service
This section briefly describes functions which may be useful for service and maintenance
of a Rosemount 5900S Radar Level Gauge. If not otherwise stated, most examples are
based on using the Rosemount TankMaster WinSetup tool to access these functions. See
the Rosemount Tank Gauging
to use the WinSetup program.
6.2.1
Viewing input and holding registers using TankMaster
™
In a Rosemount Tank Gauging system, measurement data is continuously stored in Input
Registers of devices such as the Rosemount 2410 Tank Hub, Rosemount 5900 Radar Level
Gauge, and other devices. By viewing the input registers of a device, you can verify that
the device is working properly.
Holding Registers store various device parameters used to control measurement
performance.
Procedure
1. Start the TankMaster WinSetup program.
2. In the
TankMaster WinSetup
workspace window, select the device icon.
3. Right-click and select
View Input/View Holding Registers option
, or from the
Service
menu choose
Devices
→
View Input/View Holding Registers
.
Service and troubleshooting
Reference Manual
September 2019
00809-0100-5900
188
Reference Manual
Содержание Rosemount 5900S Series
Страница 1: ...Reference Manual 00809 0100 5900 Rev EA September 2019 Rosemount 5900S Radar Level Gauge ...
Страница 6: ...Contents Reference Manual September 2019 00809 0100 5900 vi Reference Manual ...
Страница 12: ...Introduction Reference Manual September 2019 00809 0100 5900 12 Reference Manual ...
Страница 182: ...Configuration Reference Manual September 2019 00809 0100 5900 182 Reference Manual ...
Страница 186: ...Operation Reference Manual September 2019 00809 0100 5900 186 Reference Manual ...
Страница 222: ...Service and troubleshooting Reference Manual September 2019 00809 0100 5900 222 Reference Manual ...
Страница 266: ...Product Certifications Reference Manual September 2019 00809 0100 5900 266 Reference Manual ...